Chapter 9. HVAC Cooling and Heating Load Analysis

When selecting and designing HVAC systems that will serve a particular building, modeling the building accurately is key. The majority of your time during the mechanical design phase of a project is spent on properly modeling the building in a load-simulating program, such as Trane TRACE 700 or Carrier's Hourly Analysis Program (HAP), among others.

Although these programs are essential to you, the mechanical designer, setting up the building accurately within these programs often can be a tedious task. Each space is set up individually, and typically, the physical construction and use of each space will be different. Alterations to the building design or space usage by the architect during this phase will cause you to return to any previously modeled spaces and coordinate the necessary changes. This is very time-consuming and often a point of contention between disciplines when changes occur later in the design phase.

Revit MEP enables you to model the building spaces accurately, as well as quickly and efficiently track any building design and construction changes on the fly, all within the project file. Revit MEP also gives you the option to either model the HVAC loads within the program itself or export the space load data via a gbXML file to an external simulation software program.

In this chapter, you will learn to

  • Prepare your Revit MEP model for analysis

  • Perform heating and cooling analysis within Revit MEP 2011

  • Export gbXML data to load-simulating software

Modeling Spaces for Building Load Analysis

The key to any successful building load analysis lies with accurately modeling the spaces within the building. Components that need to be modeled for each space include but are not limited to building construction, such as walls, roof, floor slab, external shading and windows; internal loads, such as the number of people, the activity within the space, the heat gain from lighting, and the equipment operated within the space; and external factors, such as solar heat gain to the space, weather and typical outdoor temperatures, and infiltration. These are but a handful of factors that need to be addressed for each space that is being created, and each of these factors has several significant inputs that can affect the loads within the space.

Space Modeling

Before any HVAC loads can be run, spaces need to be created in the project file. Why? It seems redundant to create spaces, seeing as how the architectural model already has rooms created and defined, right? Not so.

In Revit MEP, spaces are not created from rooms. The same elements that define a room in the linked model define spaces in your MEP model. After you load your MEP project and link in the correct architectural model, you want to make sure that the elements that make up a room — walls, doors, ceilings, and so on — will define your MEP space accurately. Figure 9.1 shows a sample building model.

Sample building

Figure 9.1. Sample building

By selecting the architectural link in your project, the Edit Type button in the Properties palette is enabled. Clicking this will allow you to enable the selected link to be Room Bounding. This option will force the boundaries of the designed rooms to define the boundaries of the MEP spaces to be modeled. Figure 9.2 shows (a) the Edit Type button and (b) the type parameter Room Bounding.

If the link is not set to be room bounding, Revit MEP will offer a warning that the placed space is not in an enclosed region, and subsequently, if HVAC analysis is attempted, Revit will not be able to calculate load data for that space.

Placing Spaces

Revit allows you to locate the spaces within the architectural model in two ways: placing spaces manually or letting Revit locate and place spaces automatically. If your design building is complex, allowing the program to automatically place the spaces for you will save time.

Defining boundaries of MEP spaces

Figure 9.2. Defining boundaries of MEP spaces

Be sure that all the spaces created are spaces that you intend to model. Check that areas such as utility chases, furrowed columns, or air spaces in wall constructions were not included when spaces were placed. To remove any unwanted spaces from the project file, open the System Browser, which is located on the View tab under User Interface, and set the view to Zones by right-clicking the System titlebar and choosing Zones from the View drop-down menu.

Select the desired spaces to remove by highlighting the space name, right-clicking, and selecting Delete, as shown in Figure 9.3. Click OK in the pop-up window to permanently remove the spaces and any associated space tags.

If you were to just select a space within an open view and delete it without using the System Browser, the space tag and visible space marker will be deleted, but the space information will still be present in your project. This will affect any building analysis performed, as well as any HVAC systems that will be set up in the building. Systems are covered in depth in Chapter 8 and Chapter 10.

Space Properties Schedule

When simulating the heating and cooling loads of a building, correctly modeling and accounting for space usage can be time-consuming. Often, design loads have to be revisited because of inaccurate or incomplete accounting of space usage, components, internal loading, or design changes of the space use. Creating a working schedule of the building space properties in Revit MEP will help you account for and coordinate these factors.

Deleting unwanted spaces from the project file

Figure 9.3. Deleting unwanted spaces from the project file

Similar to other schedules in Revit, you are given a choice of several fields to display in the Space Properties schedule to help track and modify data pertaining to each space. Setting up a working schedule such as this one for space properties will be an essential tool that will enable you to track how changes in certain properties will affect the spaces. Note that the schedule shown in Figure 9.4 is not intended to be provided to your client on a project sheet but rather to be used as a personal design tool within Revit to help you, the designer, organize the space data to better fit your personal workflow. Create this schedule as you see fit, using the many fields, sorting, and other formatting options available to you within the program to readily organize the data you need.

Useful fields to display, during the initial space creation, include the following:

Name

Designate the space name in this field.

Number

Assign each space a number using this field.

Space Type

Describe how the space will be used in this field.

Occupiable

This is a yes/no check box that shows whether this space will be occupied.

Number Of People

Specify the space occupancy in this field.

Area

List the space area in square feet or meters.

Construction Type

Describe the space physical construction in this field. We will go over the various construction options later in this chapter.

Condition Type

Describe type of space conditioning in this field (such as Heated and Cooled, Heated, Cooled, or Unconditioned).

Sample Space Properties schedule

Figure 9.4. Sample Space Properties schedule

Modifying Space Properties

You will notice that the program defaults to a generic space naming and numbering convention when placing spaces. It also sets the Space Type and Construction Type values as <Building>, indicating that the spaces will be modeled generically, relying on default global building characteristics within the project.

How a space will be used is the overall factor driving the internal loads within a space. An enclosed office space is modeled differently than the conference room next door, and an office break room is modeled differently than a typical restaurant dining room. Lighting, population density, activity levels, equipment, and ventilation loads are all major factors that will vary with the space type.

If you open the Manage tab and then select MEP Settings

Modifying Space Properties
Building/Space Type Settings

Figure 9.5. Building/Space Type Settings

Under the Building Type category, you are able to choose a global usage for the building. This can be a good option if you want to do a quick takeoff of a typical building type for the overall model. You are given similar parameters to model as in the Space Type Settings window, as well as options to set building operating times — Opening Time and Closing Time — and an unoccupied space cooling temperature set point.

Revit MEP has several predefined options to model how each space is utilized, and each option has preset parameter and schedule values for the internal loads. Parameters such as Area per Person, Lighting Load Density, Power Load Density, and Heat Gain per Person should all be familiar to you, the mechanical designer. You may use the preset values within the program, or you are allowed to input more accurate design load values based on typical code-driven or industry-standard values.

Note that you can access the Space Type Settings window from the Properties palette when a space is selected in your view, as well as from within your space schedule by locating the cell in the Space Type column (if used in your space schedule) for the space you would like to modify and then selecting the ellipsis next to the current type name. If you click the People or Electrical Loads buttons on the space Properties palette, the default values within these windows are the values listed in the space type settings (see Figures 9.6 and 9.7).

Default Occupancy and Heat Gain values

Figure 9.6. Default Occupancy and Heat Gain values

Space Type Settings window

Figure 9.7. Space Type Settings window

Revit MEP also has default building and space schedule types that it uses to generate load data. You can modify the default schedules or create new schedules to fit your varying occupancy, power, and lighting needs. You can find Default Schedules, People Heat Gain, and Building and Space Type Data in the Revit MEP 2011 Help file, under Reference

Space Type Settings window

Zones

The next step in generating HVAC loads for your design building is to group similar spaces into zones. The main purpose of zoning spaces in an HVAC system is to provide controllability of the space air quality or condition. A single terminal unit, heat pump, or air handling unit can control the temperature and air quality of the spaces within its defined zone.

Creating HVAC zones within your building allows the designer to control the airflow to given spaces, shutting off airflow to areas that are not occupied or increasing airflow to spaces when the space load increases, via a signal from a temperature sensor or other sensing devices within the zone to a central control panel. Zoning also allows certain spaces to be controlled via a different system than the rest of the building, such as having a dining area and kitchen served via a dedicated outdoor air system that is cycled on with increasing occupancy to the space, while the rest of the building is controlled by a packaged VAV rooftop system on a typical office's 8 a.m. to 5 p.m. schedule.

Zoning spaces in Revit MEP is easy. On the Analyze tab, click Zone. This activates the Zone tool, and you are automatically prompted to add the first space to the zone. Clicking a space adds it to the zone, and then you have the option of adding other spaces to that zone. Click the Finish Editing Zone button on the ribbon to end the editing session.

Zones

To edit a zone that has already been created, simply select the required zone in the open view, and the Modify HVAC Zones tab appears. Click the Edit Zone button, and the zone creation ribbon appears. Here you are able to modify the zone by adding or removing spaces.

Zones

A second way to create a zone is to first select all the spaces you want to group together, click the Analyze tab, and select the Zone tool. Creating a zone this way automatically groups the selected spaces, without having to select each space individually with the tool active.

Selecting a zone displayed in an open view, the zone data appears in the Properties palette. From there, you are able to view the calculated heating and cooling loads and zone airflow (once Heating and Cooling Analysis has been run), the physical data of the zone (area, volume, and perimeter), and its characteristic data, which include the following:

Service Type

This drop-down allows you to select the type of system that will be serving the spaces within the zone. Revit MEP offers four groups of systems: Constant Volume, Variable Air Volume (VAV), Hydronic, and Other. Within these four options, there exist several system variations. Revit MEP automatically defaults to the service type that is selected in the Project Energy Settings window. See Chapter 2 for information on how to establish project settings.

Coil Bypass

This is where you are able to input any manufacturer's coil bypass factor for the unit serving the zone. This value indicates the volume of air that passes through the coil, unaffected by the coil temperature.

Cooling Information

This button allows you to set the space cooling set point, coil leaving air temperature, and space humidity control.

Heating Information

This button allows you to set the space heating set point, coil leaving air temperature, and space humidity control during heating.

Outdoor Air Information

This button allows you to input the ventilation loads for the space: Outdoor Air per Person, Outdoor Air per Area, and Air Changes per Hour. You may specify individual Outdoor Air options or enter a value in all three options. Revit MEP only calculates heating and cooling loads with the largest calculated outdoor airflow, not a combination of the three values. To obtain the required combined breathing zone ventilation rate as defined in ASHRAE 62.1, add the ventilation CFM needed per occupant to the CFM required per area, and divide the result per the space area. Then enter this value in either of the first two options to force Revit into calculating the code-required ventilation rate.

Building Construction

So, now all the spaces within your design building are placed, the internal data has been identified, and the spaces have been grouped into zones ready for the heating and cooling data to be analyzed. The next step is to investigate the physical construction of your building's exterior and interior walls, roofs, ceilings, glazing, doors, and floor slabs. Each of these elements controls how heat enters or leaves your design spaces to or from the surrounding outdoor environment. Each element has a specific coefficient of heat transfer, or U-value, that is dependent on the element's material composition and assembly, as well as its thickness.

But the architect who created the building elements has already defined the wall or roof construction. That data should already be loaded in with the link, right? Well, no. Although the architectural model will have accurate wall and roof constructions modeled in the linked building, the U-values will not transfer from the link. In the MEP model, the building construction parameters have to be defined by you. This will set U-values for the different elements that bound your design spaces, allowing for heat transfer into and out of the spaces to be calculated and accounted for.

To set the building construction U-values, open the Manage tab, and click Project Information.

Building Construction

From this window, click the Edit button for Energy Settings, and then click the ellipsis next to <Building> in Building Construction. This brings you to the Building Construction window (see Figure 9.8).

Once here, you will be able to define the default construction characteristics. Clicking the drop-down arrow at each category exposes a wide array of common material constructions and assemblies that you can choose from to represent the design building walls, slab, roof, and glazing, each with a unique U-value associated to it.

Unfortunately, as of this version of Revit MEP, the constructions offered for each category in Building Construction are the only constructions that are available to use. The option to edit or customize wall or roof assemblies or even to alter the thermal properties of the materials that make up the assemblies is not present in this version, nor can you enter specific U-values, such as ASHRAE Standard 90.1 building envelope values. As the designer, you must choose the construction option that is closest to the actual U-value that has been calculated through material thermal takeoffs of the architectural design.

Just as all spaces are not going to be conditioned alike, some spaces have a different physical construction than the rest of the design building. For example, a utility space such as a mechanical or electrical room typically can be seen with exposed block wall construction, bare floor slab, open roof trusses or beams, and little or no insulation on the exterior walls. In Revit MEP, just as the individual space types can be defined differently from the overall building type, each individual space has the option to define its own construction U-values.

To alter the space construction, select a space in an open view; or, if you have created a Space Properties schedule, select the ellipsis next to <Building> in the Construction Type column of the space that you want to edit. The Construction Type window will open, and here you will be able to create individual space construction types as needed (see Figure 9.9).

Building Construction window

Figure 9.8. Building Construction window

The same construction categories and options exist here that are available in the Building Construction window. Create as many different constructions as needed, and if there exists, in your design building, several spaces that utilize a different construction from the main building, you will be able to easily select the appropriate construction from your created list. Note that you are not able to alter the default <Building> construction type in this window. This is accessed from the Building Construction window, mentioned earlier.

Performing Heating and Cooling Load Analysis

Now you have all your design spaces created and respective parameters, conditioning systems, and space constructions defined. The next step then is to pull all this data together into a heating and cooling load analysis report to tell you how this particular building will perform throughout the year. You will then use that data to further refine your conditioning systems as well as size the equipment you will assign to your HVAC zones.

We've already discussed how the building and space construction can be modified to suit your building. But how do the different construction options affect the heat transfer into or out of the space? The engine that performs the heating and cooling load analysis in Revit MEP 2011 uses a Radiant Time Series (RTS) method to determine the building and space peak heating or cooling loads. This method takes into account the time delay effect of heat transfer through building envelopes, from the outside, and into spaces. A brief explanation of this method follows, but the RTS method of calculation is defined in detail in Chapter 30 of the 2005 ASHRAE Handbook of Fundamentals, as well as in the Load Calculation Applications Manual, also published by ASHRAE (visit www.ashrae.org for details).

Construction Type window

Figure 9.9. Construction Type window

The RTS calculation method determines cooling loads based on an assumption of steady periodic conditions, such as occupancy, design day weather, and cyclical 24-hour heat gain conditions. Two time-delay effects are addressed during cooling load calculations:

  • Delay of conductive heat-gain through opaque massive exterior surfaces, such as exterior walls, the building roof, and floor slab on or below grade

  • Delay of radiative heat gain conversion to cooling loads

Figure 9.10 shows a flow chart summarizing the RTS calculation method.

Exterior building elements conduct heat because of a temperature differential between indoor and outdoor air; solar energy is absorbed by exterior surfaces as well. Since each surface has a mass and an associated thermal capacity of the materials that make up its construction, a time delay occurs from when the heat input of the outdoor and solar loads becomes heat gain to the interior space. The majority of energy transferred to a space as heat is by a combination of convection and radiation — the cooling load immediately picks up the convective part of the energy transfer, and any radiant heat is absorbed into the surrounding space constructions and interior room finishes.

Radiant Time Series (RTS) calculation flow chart

Figure 9.10. Radiant Time Series (RTS) calculation flow chart

The radiant heat is then transferred via convection to the space from those surfaces at a delayed time. Interior loads contribute to both the sensible heat gain of the space as well as a latent heat gain that is given off by people activity within the space. The latent heat gain contributes to the instantaneous cooling load of the space, while the sensible heat gain from internals is absorbed and retransmitted by radiation to the space.

The engine sums up the calculated cooling loads to determine a total cooling load per each design hour, and it selects the highest load, or peak, for the design of the air-conditioning system. Note that Revit MEP 2011 uses, for the standard calculation, the hours of 6 a.m. to 6 p.m. for the design day, not the full 24 hours, and only the months of April through November (October through May for southern hemisphere locations), not the full calendar year. The design day is derived from weather data for the location that you set during project establishment. We will revisit weather data later in this chapter.

Heating loads are calculated much the same way. The major differences are the obvious lower outdoor air temperatures in the heating design day, solar heat gains and internal heat gains are ignored, and the thermal storage effect of the building construction is not included. Negative heat gains, or heat losses, are considered to be instantaneous; therefore, heat transfer is dealt with as conductive. Latent heat gains are treated as replacing any space humidity that has been lost to the outdoor environment.

The worst-case load, as determined by the Revit MEP engine, is based on the design interior and exterior conditions and loads due to infiltration or ventilation. Solar effects are ignored — assuming night or cloudy winter day operation — and Revit does not recognize any internal heat gain from people, lights, or miscellaneous equipment to offset the heating load needed.

Load Analysis

You now have a complete building modeled and ready to analyze. The next step is to verify and specify, if needed, the building energy parameters, as shown in Figure 9.11. On the Analyze tab, click the Heating And Cooling Loads button. The Heating and Cooling Loads window will appear, and on the General tab, you will be able to view the building energy analysis project information that directly affects the heating and cooling analysis. You can also access these parameters through the Manage tab's Project Settings

Load Analysis
Heating and Cooling Loads window

Figure 9.11. Heating and Cooling Loads window

In this window, you are able to set parameters such as the global building use type, building location, the global conditioning system, overall building construction and ground plane, the ground level reference, and building infiltration. You are also able to define the level of load analysis report detail you want to see.

Weather Data

We discussed earlier in the chapter building type, service type, and building construction, but another major component of energy analysis is the physical location of the building. The location determines environmental conditions such as outdoor air temperature and humidity and also ASHRAE climate zone data. To define the building location, click the ellipsis next to the city and state in the Location cell. You will be taken to the Location dialog box, as shown in Figure 9.12.

You have two ways to input the project design city: select the location from the default city list, or use the Internet mapping service, as shown in Figure 9.12. If you are connected to the Internet, this option allows you to locate your project using an interactive map through the Google Maps mapping service. The default city list contains major cities from which to select your project location. Select the major city from the list that is nearest to the project location address, or, if it is known, you can enter the latitude and longitude coordinates for a more exact location. Select Use Daylight Savings Time if it is appropriate for your project location.

The next step is to modify the cooling and heating design temperatures, if needed. You may use the default values that are associated with the closest weather station to your design city; or, by deselecting that option, you are able to modify the Dry Bulb, Wet Bulb, and Mean Daily Range temperatures as needed to fit your design location. You may specify the Heating Design Temperature value and set the Clearness Number value, which ranges from 0 to 2, with 1.0 being an average clearness. Clearness is defined in section 33.4 of the 2007 ASHRAE Handbook – HVAC Applications in the following way:

Greater than 1.2

Clear and Dry

1.0

Average

Less than 0.8

Hazy and Humid

Location Weather and Site

Figure 9.12. Location Weather and Site

Outdoor Air Infiltration

The Building Infiltration class needs to be set next. You are given four choices to model the rate of outdoor air that enters the building, typically through leaks in the building envelope created at envelope openings such as windows, doors, and where perpendicular building surfaces join. In Revit, infiltration is defined with the following categories:

Loose

0.076 CFM/ft2 of outside air.

Medium

0.038 CFM/ft2 of outside air.

Tight

0.019 CFM/ft2 of outside air.

None

Infiltration air is excluded from the load calculation.

Sliver Spaces

The next parameter to define is Sliver Space Tolerance. Sliver spaces in Revit are considered to be narrow areas that are bounded by parallel interior room-bounding components — parallel interior walls. These spaces include, but are not limited to, pipe chases, HVAC shafts, furrowed columns, and wall cavities. A sliver space is included in the heating and cooling load analysis only if identical parallel room-bounding elements enclose the space, the width of the sliver space is equal to or less than the Sliver Space Tolerance parameter, and if a space component has been placed in the tangent spaces on either side of the sliver space. If any one of these three requirements is not satisfied, Revit does not recognize any effects of the sliver space. If there are different geometries to the same sliver space, only the areas of the space that meets the previous criteria is counted in the load analysis. The sliver space volumes are added to the volume of the larger tangent analytical spaces.

Define the detail level of the heating and cooling analysis report. Three report detail levels are available: simple, which contains summary data for systems, zones, and spaces; standard, which expands the simple report to include psychrometric data as well as building level summaries and load summary data for each space; and detailed, which further expands the data displayed to include individual component contributions to zone and space loads.

Before you finish, define the ground plane, project phase, and whether to include heating or cooling load credits, which are negative load values that come from heating entering or leaving a space through a partition into another zone, for example.

Details

Before you analyze the building performance, you are given the opportunity to go through your created zones and spaces to make sure your desired settings have not been compromised and to make sure there are no warnings that would produce undesired effects on your loads. Switching to the Details tab, you can view the space and zone data that directly affects the heating and cooling analysis, as in Figure 9.13.

Building model details

Figure 9.13. Building model details

Selecting a zone, you are able to expand the tree to view the associated spaces and verify or modify the zone service type, heating, cooling, and outdoor air information as needed. You can see whether a space is occupied, unoccupied, or a Plenum space by the symbol preceding the space name in the tree.

Building model details

If a space is selected, you can set the space and construction type, as well as internal load information. If, when expanding a zone, a warning symbol appears alongside a space, you are able to investigate by clicking the Show Related Warnings symbol and then correct or ignore the cause of the warning (see Figure 9.14).

Warning

Figure 9.14. Warning

The Space Warning shown in Figure 9.14 suggests that a space exists without an upper bounding element. Click the Save Settings button, and you will be directed back to your model. Locate the space in question, and verify that the upper limit of the space is correct through the space Properties palette. You can also inspect the space visually by creating a section view through the space and verifying that the upper limit extends past a bounding element in the linked model.

Opening the Heating and Cooling Loads window and selecting Analytical Surfaces allows you to view and isolate the physical elements that bound the spaces to be analyzed. You are able to isolate every individual bounding element that has been defined for the space — roofs, exterior and interior walls, ceilings, floors, and any air gaps or sliver spaces — and view them for any modeling errors, before the simulation is performed.

Heating and Cooling Loads Report

Go ahead, click the Calculate button.

After the simulation is completed, you are directed to the Heating and Cooling Loads report, as shown in Figure 9.15. Depending on the level of report detail you selected prior to running the simulation, the tabulated results will be shown, broken into an overall project summary, a building summary, building level summaries, individual zone data, and individual space data.

Sample Heating and Cooling Loads Report

Figure 9.15. Sample Heating and Cooling Loads Report

The Project Summary area lists the project information (name, address, location), as well as calculated design date and time, Summer Dry Bulb and Wet Bulb temperatures, the Winter Dry Bulb temperatures, and the Mean Daily Range — values that should match the inputs you have entered with the weather data. The Building Summary area includes the global building type and its total analytical area and volume, as well as the overall calculated performance of the building — Peak Cooling Loads, Peak Heating Load, Airflows, and building checksums.

The Level Summary area includes the analytical area and volume of each level of the design building, if applicable, as well as each level's individual performance values, similar to the Building Summary. The Zone Summary lists each analyzed zone, listing its inputs, psychrometrics, and the calculated performance results. It also breaks down the various cooling and heating components and displays a list of the spaces that make up the zone along with a brief summary of the space performance. The Space Summary displays the space analytical areas and space volume, load inputs, and space type, as well as the calculated results for the space. It, too, contains a breakdown of the individual space components and how they contribute to the cooling and heating loads.

Revit MEP allows you to run a heating and cooling load analysis, make changes, and run subsequent analysis all while retaining the reports run for each analysis. Load reports are individually timestamped and can be accessed in the Project Browser under Reports. This enables you to easily flip to a previous report and quantify the changes in your design, without resorting to printing out each report as it is generated. Each report can grow to several hundred pages in length, depending on the size of your job and the detail level selected.

Now is a good time to set up and run a sample HVAC load analysis in Revit. Here's how:

  1. Create a new Revit MEP 2011 file.

  2. Link in the Architectural model file ch9ArchModel.rvt on the book's download page, http://www.wiley.com/go/masteringrevitmep2011. Use Origin To Origin placement.

  3. Set the property of the linked file to Room Bounding by selecting the link, editing its Type Parameters, and checking the Room Bounding box. Click OK.

  4. Place your spaces. Click the Analyze tab, and select Spaces to begin placing your spaces in the view. Either select the rooms you want to model, or click Place Spaces Automatically. Confirm the number of spaces created.

  5. Create a working Space Properties schedule to manage space data. Click the Schedule/Quantities button.

  6. Select Spaces as the category, and use New Construction as the phase. Click OK.

  7. From the available fields, select the appropriate categories to match the Space Properties schedule shown in Figure 9.4.

  8. Adjust the Name and Number fields to match the architectural link, either by manually entering the values or by using a space naming utility. Sort the rows in descending number order.

  9. Notice that all the space types are set to <Building>, and the condition type is Heated and Cooled. If you examine the building type, you should see that it is set to Office. Select Manage

    Sample Heating and Cooling Loads Report
  10. In the Space Properties schedule, select the space type cell associated with Office 102. Open the Space Type Settings dialog box by clicking the ellipsis in that cell.

  11. Set the space type to Office – Enclosed. Notice the changes in the space parameter values. Verify that the Occupancy schedule is set to Common Office Occupancy – 8 AM to 5 PM and that the Lighting and Power schedules are set to Office Lighting – 6 AM to 11 PM. Click OK.

  12. Notice the Number Of People value for Office 102 has changed. This reflects the different Area Per Person parameter value for the Space Type – Office vs. the Building Type – Office.

  13. Set the remaining space type values appropriately.

  14. Notice that the number of people in each space is taken out to six decimal places. Set the field format for this column to use fixed units with a rounding to 0 decimal places. Switch back to the 1-Mech floor plan view.

  15. Click the Heating and Cooling Loads button on the Analyze tab. Switch the view to Details, and expand the Default tree.

  16. Each space has a warning symbol attached to it. Select a space. Clicking the Warning button, you will see that the space is not upper bounded by a roof, ceiling, or floor element. You need to set the upper limits of each space to ensure accurate building analysis. Click OK and then Cancel.

  17. In the 1-Mech floorplan, select all the spaces. In the Properties palette, set the upper limits of each space to Level 2, with a 0'-0" offset.

  18. Open the Heating and Cooling Loads window, and verify that all the warnings have been cleared from the spaces.

  19. Click Calculate.

  20. View the building performance report that has been generated.

  21. Switching back to the 1-Mech floorplan, click the Zone button on the Analysis tab.

  22. Create zones in the 1-Mech floorplan. Group the spaces as shown in Figure 9.16, and name the zones per the sample schedule.

    Grouping spaces in the floorplan

    Figure 9.16. Grouping spaces in the floorplan

  23. Select Zone 05 in the floorplan. Verify that the service type is VAV-Terminal Reheat and that the Cooling and Heating Information settings are both Default.

  24. Click Edit for the Outdoor Air Information, and, for this zone, enter 5 CFM per person, and 0.06 CFM/SF in the appropriate boxes. Set the space occupancies equal to 1 person.

  25. Run another building analysis.

  26. Viewing the Zone Summary report for Zone 05, you should see that the Peak Ventilation Airflow is 20 CFM. The Ventilation Density value will equal 0.06 CFM/SF, the value you entered. The Ventilation/Person value, however, will equal 7 CFM/person, which is not what was entered. Remember, Revit MEP takes the largest ventilation load, not the required combined ventilation load, when calculating the building performance.

  27. To get the ASHRAE required ventilation, do the following:

    1. Calculate the required ventilation from area.

    2. Calculate the required ventilation from occupants.

    3. Add the two values, and divide by the total area.

    4. Enter this value in the Outdoor Air Information window for Zone 05.

  28. Run the analysis again, and observe that Zone 05 Ventilation Airflow has changed to the airflow calculated in the previous step.

  29. Using the space properties schedule, zone properties, and the heating and cooling loads window, adjust various parameters, and rerun the heating and cooling analysis.

  30. Use the different reports generated to compare the effects of your changes to the building.

  31. Close the file.

Exporting gbXML Data to Load-Simulating Software

Now we've explored how to set up a building for heating and cooling load analysis and how to perform the analysis in Revit MEP 2011. That's it, right? You're done? You have an accurate energy analysis of every component in the building heating and cooling systems?

Unfortunately, the engine built into this version of Revit MEP does not have the programming to perform a complete energy analysis of your building. Increasing LEED certification requirements need an equally increasing level of detail in the building analysis, comparison to baseline building design, and documentation to obtain the desired design certification. The solution to this dilemma is to export your Revit MEP model via gbXML format to a third-party simulation program, such as Trane TRACE 700 or Carrier's Hourly Analysis Program (HAP).

gbXML, or the Green Building XML schema, was developed in the late 1990s to enable interoperability between building design models and engineering analysis tools. Its use by major CAD vendors and several major engineering simulation vendors helps to streamline time-consuming building takeoffs — helping to remove some of the cost associated with the design of energy efficient buildings. Go to http://gbxml.org/ for more details on the purpose and origin of gbXML.

To export your Revit MEP model, click

Exporting gbXML Data to Load-Simulating Software

This window looks nearly identical to the Heating And Cooling Loads window (shown earlier in Figure 9.11). If a heating and cooling load analysis has already been performed, the majority of the parameters in the General tab should already be defined per your design requirements. If not, these parameters have been discussed earlier in this chapter. Adjust the parameter values as needed.

Export gbXML window

Figure 9.17. Export gbXML window

Two parameters that do not exist in the analysis window are Export Default Values and Export Complexity. If the Export Default Values box is selected, the default values for people, electrical loads, occupancy, lighting, schedules, and constructions will be exported, regardless of any user-overridden values. If this box is cleared, then only user entered values will be exported.

Export Complexity is simply that: the level of complexity of the information contained within the exported gbXML file. Five levels of complexity exist and are described here:

Simple

Curtain walls and curtain systems are exported as a single opening. Simple complexity is used for the heating and cooling analysis and is most suited for exporting.

Simple With Shading Surfaces

This is the same as Simple, but with shading surface information included.

Complex

Curtain walls and panels are exported as multiple openings, each panel as a separate opening.

Complex With Shading Surfaces

This is the same as Complex, but with shading surface information included; however, the shading surfaces (roof overhand, free-standing wall, and so on) are not associated with any room/space.

Complex with Mullions and Shading Surfaces

This is the same as Complex With Shading Surfaces, but with mullions and curtain walls exported as simple analytical shading surfaces based on centerline, thickness, and offset.

The Details tab is identical to the analysis window, and as before, you are able to set or verify space energy parameters such as the building and space construction types, internal loads, and zone information like the service type and temperature set points. You are able to view and verify that all the analytical surfaces are correct and address any construction or space modeling warnings that are present before exporting.

Clicking Next, you are prompted to save the gbXML file. Browse to your project directory, and name the file accordingly. Your gbXML file is now ready to use.

Now you have complete model information set up to be read by a simulation program without issue and without any further manipulation. Right? Unfortunately, that is not the case.

A major issue with the exported data deals with the building construction. Revit breaks larger elements, such as the floor slab in large or complex-shaped space, into smaller polygonal elements for computation. This means that a single floor element is broken into several, individually tagged and defined, floor elements in the same space. Revit MEP also has a tendency, depending on how the architectural link is modeled, to assign exterior wall values to interior walls or roof values to ceilings that bound a space.

If your design space has an unusual or atypical geometry, such as a curved wall, the number of individual elements within a single type can grow to the hundreds. This is a prevalent issue when trying to import your gbXML file into an outside simulation program. There simply is not enough capacity of the third-party programs to handle large numbers of building surfaces — sometimes stopping at the first eight surfaces and causing you, the designer, to have to examine each space individually to delete and remodel any surfaces in error.

Also, importing errors may occur when parameters such as the construction data U-values fall outside a common range predefined by your simulation software. Often it will prompt a warning message, but other times, the gbXML data will fail to import completely. Most of the time, the remedy again is to check each individual building element construction or assembly to make sure that the appropriate U-values are modeled. Otherwise, you are forced to manually create the assemblies from scratch. In addition to checking the construction, make sure the internal load data has been properly read by your simulation program — manually adjust or enter the data as required.

Do not be discouraged. Yes, there are some drawbacks and trip-ups that may occur with exporting and importing gbXML data from Revit. As a designer, any effort you make to reduce the time-consuming process of modeling each space of the building in your simulation program will be worth the effort. Although there are some shortcomings, with Revit MEP 2011 you have the ability to examine the model geometry and data within the space prior to analysis, which can save time on your projects and increase coordination.

The Bottom Line

Prepare your Revit MEP Model for analysis

The key element to a successful building performance analysis is the proper accounting of all variables that will influence the results.

Master it

Describe the relationship between rooms and spaces — are they the same element? Describe an essential tool that can be created to maintain and track space input data and building construction for a heating and cooling load analysis.

Perform heating and cooling analysis with Revit MEP 2011

Before a piece of equipment can be sized or duct systems designed, the building heating and cooling performance must be known in order to accurately condition your spaces.

Master it

How does project location affect building heating and cooling loads? Describe methods to determine project location in Revit MEP 2011.

What is a sliver space, and how does it affect the building performance?

Export gbXML data to load-simulating software

Often, to complete the building analysis, the Revit MEP model has to be analyzed in greater detail by a third-party simulation program.

Master it

What is gbXML? Why is it necessary to export your Revit MEP project?

..................Content has been hidden....................

You can't read the all page of ebook, please click here login for view all page.
Reset