Equal area criterion (EAC) is the graphical interpretation of transient stability of the system. This method is only applicable to a single machine connected to an infinite bus system or a two-machine system. The concept of EAC is derived from the fact that the stored kinetic energy in the rotating mass tries to substantiate the imbalance between the machine output and input. A single machine connected to a large system such as an infinite bus is considered to explain the EAC concept.
Consider a synchronous machine connected to an infinite bus. Neglecting the damping effect, the swing equation is rewritten below.
where Pa is the accelerating power, which is due to imbalance between mechanical input and electrical power output. From the above equation,
Multiplying both sides of the above equation by 2. we get
The above equation can be written in the modified form as:
or
Integrating both sides,
or
Under stable conditions of the machine, the variations in the rotor speed (or ) must be equal to zero. This is possible only when the right hand side terms of Equation (9.3) is zero.
i.e
The Swing Curve
It is a graph indicating the variations in δ with time t.
Fig 9.1 Swing Curve for Stable and Unstable Power Systems
The swing equation indicates that the rotor shall either accelerate or decelerate when there exists an imbalance between mechanical input and electrical power output. Due to this, the rotor may run above or below the synchronous speed, indicating system instability as shown in Figure 9.1.
Stability/Instability Conditions
Graphical Interpretation of EAC
Consider the power-angle curve of an alternator as shown in Figure 9.2
Initially the machine is operating at the equilibrium point A, where Pe0 = Pm0 and δ = δ0 as shown in Figure 9.2. Now, the mechanical input to the machine is suddenly increased from Pm0 to Pm1. As Pm1 > Pc0, the value of accelerating power Pa is positive and hence the rotor starts accelerating. Due to this acceleration of the rotor, δ increases as shown in Fig 9.3.
Fig 9.2 Power Angle Curve of an Alternator
Fig 9.3 Rotor Movement from Point A to B
With an increase in δ, Pe increases. When δ reaches δ1 (at point B), the accelerating power Pa becomes zero as Pe = Pm1. At point B, the rotor speed is above synchronous speed and due to inertia it continues to move forward beyond point B. For δ > δ1, Pe > Pm1, and PA is negative. Hence the rotor starts decelerating. Beyond point B, the rotor speed is decreases due to deceleration.
The rotor speed reaches Ns at point D. At this point, as Pe > Pm1, the rotor continues to decelerate and δ starts decreasing as shown in Fig 9.4.
Fig 9.4 Rotor Movement from Point D to B
When the rotor reaches point B from D, Pe again equals to Pm1, hence Pa becomes zero. However, due to inertia the rotor continues to move beyond point B towards A and acceleration begins.
The result is that the rotor swings from A to D via B, and from D back to A.
Considering losses (which give damping effect to the rotor), the rotor finally settles down at a new equilibrium point B after performing the swing as explained.
It can be observed that the rotor accelerates when it moves from A to B and decelerates when it is moves from B to D. From the laws of mechanics the machine swings stably when the excess energy stored in the rotating mass while it accelerates is equal to the energy it gives up during deceleration.
Mathematically,
|area A1| = |area A2|
This is known as the equal area criterion.
From EAC, the condition for stability can be stated as follows:
“The accelerating area (positive) under the P − δ curve must be equal to decelerating (negative) area”.
Now we consider the various types of disturbances on a single machine connected to an infinite bus (SMIB) system and analyse its stability by using the EAC criterion.
Case-1: Mechanical input to the rotor is suddenly increased
Consider the SMIB system shown in Figure 9.5
Fig 9.5 An SMIB System
Electrical power transmitted to the infinite bus is given by
Initially the system is operating stably, at which
This initial steady point is marked as point A on the P-δ curve shown in Figure 9.6.
Fig 9.6 Power Angle Curve of an SMIB System for a Sudden Increase in Mechanical Input to the Generator
Now, the mechanical input to the generator is suddenly raised to pm1 from pm0 by opening the steam valve. Consequent to this change, the following sequence of changes takes place.
Stage-1: At point A
The system is under steady-state with perfect balance between Pm0 and Pe0 and Pa = Pm0 − Pc0 = 0. The speed of the rotor equals to the synchronous speed NS . Now, the mechanical input to is raised suddenly to Pm1 from Pm0.
Stage-2:Movement from point A to B
Though the mechanical input to the rotor is increased, the generator cannot generate extra electrical power, since δ cannot change instantly due to rotor inertia. Hence, the extra mechanical input Pm1 − Pm0 is stored as kinetic energy within the rotor and therefore the rotor starts accelerating. The speed of the rotor is now above NS and hence Pe now starts increasing. But the accelerating power begins to reduce as the imbalance between Pm and Pe starts reducing due to an increase in the Pe value.
Stage-3:Reaching point B
On reaching point B, δ value equals to δ1 and the electrical power output Pe is raised and made equal to Pm1. The rotor now stops accelerating as Pa value is zero. At this point it should be remembered the speed of the rotor is above NS . Though Pa value is zero, δ continues to increase beyond δ1 as the forward movement of rotor continues due to inertia of the rotor.
Stage-4:From point B to C
On leaving point B, δ increases beyond δ1. Due to this, the machine now generates electrical power output more than Pe1. The Pa value is now negative as Pe > Pm1. Due to this the rotor now starts decelerating. It should be noted that though the rotor is decelerating, it still moves in the forward direction (δ increasing) as the speed is more than NS .
Stage-5:Reaching Point C
On reaching point C, δ value reaches δ2. Now the speed of the rotor is equal to NS.
As δ2 > δ1, the electrical power output is more than the mechanical input and hence the Pa value is negative. The rotor now decelerates in the reverse direction (δ decreasing) and the negative value of Pa begins to reduce.
Stage-6:From point C to B
On leaving point C, Pe value begins to reduce as δ value is decreasing. This is because the rotor is moving in the backward direction. The decelerating power Pa begins to reduce. However the rotor speed is now lesser than NS, as the rotor is moving in backward direction.
Stage-7:Reaching point B
On reaching point B, the Pe value becomes equal to Pm1 and hence Pa value is zero. The rotor speed is still less than Ns and the rotor continues to move in the backward direction (δ decreasing) due to inertia.
Stage-8:From point B to A
On leaving point B, δ value becomes less than δ1, and consequently, Pe value is less than Pm1. Now the Pa value is positive and the rotor begins to accelerate with the rotor speed again starting to increase.
Stage-9:Reaching point A
When the rotor reaches point A, δ value is equal to δ0 and the rotor speed rises to NS. It should be understood that while the rotor is moving from point B to A, though its movement is backward it is actually accelerating. Once it reaches the point A, the movement in the backward direction stops and it begins moving in the forward (δ increasing) direction.
This completes one cycle of operation and Stages 1 to 9 are repeated again. If the system damping is considered, these oscillations gradually die out and the machine will settle to the new equilibrium point B
where Pm1 = Pe = Pmax sin δ1
The steps related to the swinging of the rotor are depicted in Table 9.1.
The areas A1 and A2 are given by
For the system to be stable A1 = A2
Table 9.1 Steps related to the swinging of the rotor
Condition of maximum swing
From the steady-state stability point of view, the system reaches the critical stable point when δ = 90°. However, the system can maintain transient stability beyond δ = 90°, as long as the condition of EAC is satisfied. Figure 9.7 illustrates this.
Limitation to increase in Pm value
Consider the swing curve shown in Figure 9.7.
For the given value of δ0, an increased value of Pm is such that, if δ goes beyond δm the system loses transient stability. At point B, Pe1 = Pm1 = Pmax sin δ1. At point C, Pc1 = Pm1 = Pmax sin δmax. It can be easily verified that the above equations are valid only when δmax = π − δ1. Considering the P − δ curve shown in Figure 9.7, if Pm value is increased beyond Pm1 as shown, then the rotor swings beyond δm. However, if δ becomes greater than δmax, then the power transfer will be lesser than Pm and the rotor will experience further acceleration. This will further increase δ and the generator will be out of synchronism (See Figure 9.8).
Fig 9.7 The System has Transient Stability when the Rotor Swings beyond δ = 90°
Fig 9.8 Limiting Case for Increase in Pm
Therefore, the limiting value of Pm1 for a given Pm0 can be computed by the condition.
where
Case-1: Mathematical Equations for EAC
Accelerating area
Decelerating area
The system is stable when A1 = A2 i.e., pmax(cos δ0 - cos δ2) = pm1(δ2 - δ0). Substituting pm1 = pe1 = pmaxsin δ1 in the above equation,
For the limiting case,
Therefore,
For the given value of δ0, the value of δ1 cannot be found directly. Equation (9.13) can only solved by the iteration process.
Case-2: Three-Phase Fault on Feeder
Consider Figure 9.9(a) where a generator is connected to an infinite bus bar through a radial feeder.
The p-δ curve is shown in Figure 9.9(b).
Let the system shown in Figure 9.9(a) be operating at point A, where the rotor speed is equal to NS and δ = δ0.
Now, a 3-phase fault occurs at point F on one of the outgoing feeders. Since the fault is closer to the generator and as resistance is being neglected, Pe instantly becomes zero. In other words, no electrical power is transferred to the infinite bus.
Fig 9.9(a) A Three-Phase Fault at Point F on an SMIB System
Fig 9.9(b) p-δ Curve
Now, the entire Pm becomes equal to Pa, and the rotor starts accelerating. Since Pe = 0, the operating point shifts immediately to point B and due to rotor acceleration, δ starts increasing. In time tcr (critical clearing time) when the rotor angle reaches to δcr (critical clearing angle), the circuit-breaker installed at point F clears the fault by isolating the faulted line. Upon removal of faulted line, the generator once again starts transmitting power to the infinite bus. Therefore, the operating point shifts from C to D instantly. At point D, since Pe > Pm, the rotor now begins to decelerate and the decelerating area A2 begins as the operating point moves along D−E.
System is stable as long as A1 ≤ A2
For a given initial load there is a maximum value of clearing angle, known as critical clearing angle (δcr) for stability to be maintained. If the actual clearing angle δ1 is smaller than δcr, the system is stable. If δ1 > δcr the system is unstable. It should be noted that when δ1 = δcr, the rotor swings up to δmax, a permitted threshold value. Beyond δmax, the stability of the system is lost. The circuit-breaker fault clearing time corresponding to δcr is known as the critical clearing time (tcr). If the actual fault clearing time is less than tcr, the system is stable, otherwise it is unstable.
The formulas for δcr and tcr can be easily derived only for the case when Pe = 0. For other cases it is hard to establish the formulas.
Fig 9.10 A Simple Case to Determine Critical Clearing Angle δcr
The following equation can be easily verified in the p-δ curve shown in Figure 9.10
From the above,
Now, accelerating area
Since Pe is zero,
Decelerating area
For the system to be stable, A2 = A1, which yields the following relation
where δcr = critical clearing angle.
By substituting δmax = π − δ0 and Pe = Pm = Pmaxsin δ0 in Equation (9.16),
We get,
Note: The value of δcr depend upon initial loading condition of machine. In other words depends on the initial value of δ0.
During the fault on the system,
Therefore,
Substituting
Integrating the above equation twice,
From the above,
Case-3: Loss of Faulted Parallel Line
Consider the power system shown in Figure 9.11. The generator is connected to the infinite bus system through two parallel lines.
Fig 9.11 Three-Phase Fault occurs at some Point on One Parallel Line of the SMIB System
Now, consider a fault at point F some distance away from both ends on one parallel line as shown in Figure 9.11.
Before fault
During fault
Let the transfer reactance during fault be Xdu. Its value can be obtained by converting star reactances X'd, X1 and X21 into delta. This is explained in the following figure.
Post fault:
After some duration, the faulty parallel line is removed by circuit-breakers connected at both ends. The transfer reactance for this condition Xpo is:
The steady-state power limits for these conditions are given below.
Fig 9.12 p–δ Curve for Case-3 Study of EAC
Now consider the p-δ curve shown in Figure 9.12.
Assume that the input power Pm is constant and that the machine is operating steadily, delivering power to the infinite bus at δ = δ0. The p-δ curve for the pre-fault condition is marked as a in the figure. During fault condition, equivalent transfer reactance between bus bars is increased, lowering the steady-state power limit. For this condition the p-δ curve is represented by the curve B. Finally curve C represents the post-fault p-δ curve.
The following sequence of operations takes place.
System is stable when A1 (accelerating)
= A2 (decelerating)
i.e., Area a b c d = Area d e f
Applying EAC, for this case δe can be obtained as follows,
where
Integrating Equation 9.19,
or
Case-4: Re-Closure Operation of Circuit Breaker
Considering the fault as temporary, circuit breakers in the faulted line are re-closed after some time. As the fault is cleared, the line is restored into service again.
For this case, p-δ curves for before the fault and after re-closure are the same.
i.e.,
The p-δ curve is drawn for the case in Figure 9.13.
The stability of the system improves, as the re-closure unit of the circuit breaker restores the second line back into service for transfer of electrical power.
Fig 9.13 Case-4 of EAC: Application of the Re-Closure Unit
The following is the sequence of operations for this case study:
A generator is generating 20% of the maximum power it is capable of generating. If the mechanical input to the generator is increased by 250% of the previous value, calculate the maximum value of δ during the swing of rotor around the new equilibrium point.
Solution:
The p-δ curve is shown in Figure 9.14
Fig 9.14 P-δ Curve
At Point a,
At Point b,
Now, we are required to find δ2.
For the system to be stable,
Accelerating area A1 = Decelerating area A2
The value of δ2 may be found using the numerical method or the trial and error process. Here δ2 determined by the trial and error process.
From the condition δ2 > 0.5235, the starting value of δ2 is guessed as 0.55
δ2 | X = 0.5 δ2 + cos δ2 | X - 1.08 = error |
---|---|---|
0.55 | 1.1275 | 0.04752 |
0.57 | 1.1269 | 0.0469 |
0.6 | 1.12533 | 0.04533 |
0.7 | 1.1484 | 0.0348 |
0.75 | 1.10668 | 0.02668 |
0.77 | 1.1029 | 0.0229 |
0.78 | 1.10483 | 0.0248 |
0.79 | 1.10091 | 0.0209 |
0.8 | 1.0967 | 0.016 |
0.85 | 1.0849 | 0.0049 |
0.86 | 1.08243 | 0.00243 |
0.87 | 1.0789 | 0.0001734 |
From the tabulated results the approximate value of
Consider the power system shown in Figure 9.15
Fig 9.15 An SMIB Power System
The p.u reactances are marked in the figure. A balanced three-phase fault occurs at the middle point of Line-2. The generator is delivering 1.0 p. u. power at the instant preceding to fault. By the use of equal area criterion, determine the critical clearing angle.
Solution:
Before fault condition:
During fault condition:
For a fault at the middle of Line-2 the equivalent circuit is as shown in Figure 9.16 below.
Converting star reactances of 0.2, 0.4 and 0.2 p.u into delta, the transfer reactance can be obtained from this equivalent circuit.
Fig 9.16 Determination of Transfer Reactance
Steady-state power limit for the condition is:
Post-fault condition:
The fault in Line-2 is removed by opening the circuit breakers at both ends. The transfer reactance for this case is:
The three power angle curves are shown in Figure 9.17(a).
Fig 9.17(a) Power Angle Curves for a Fault at the Middle of Line-2
Under steady-state conditions prior to fault,
Now, we are required to find δcr with 5 reference to Fig 9.17(b)
Fig 9.17(b) Determination SCR
The maximum angle up to which the rotor can swing for a given value of δ0 is:
Accelerating area
Decelerating area
For the system to be stable,
By integration,
Solving the above equation,
In the above example, find the critical clearing angle if a three-phase fault occurs on Line-2, close to the generator.
Solution:
In this
Consider the system shown in Figure 9.18.
Fig 9.18 An SMIB System
The per unit values of different quantities are:
The system is operating stably with a mechanical input of Pm = 1.4 p.u. Now, one of the lines is suddenly switched off.
Solution:
Fig 9.19 P—δ Curve
Before Line-2 is switched off:
Transfer reactance = 0.1 + (0.6||0.6) = 0.4 p.u
After Line-2 is switched off:
Transfer reactance = 0.1 + 0.6 = 0.7 p.u.
As the mechanical input is constant before and after Line-2 is switched off, the generator generates the same amount of electrical power output. The initial equilibrium point is a and the final equilibrium point is c as shown in the figure.
i.e.,
From the above, δ1 can be determined
Or, δ1 = 54.77°
If stability is of interest, the rotor can swing to a maximum of δmax (up to point f).
At point c and f, the Pe generated is same.
Solving, δmax = π − δ1 = 2.186 rad or 125.3°
The accelerating area A1 is:
System stability depends on whether or not there is sufficient decelerating area A2 available. In other words, for the system to stable the condition is A1 ≤ A2
Maximum decelerating area available, A2,max, can be found as:
Since A2max > A1 the system is stable.
The above equation cannot be solved directly. Iterative methods are required to obtain δ2. An approximate value δ2 is obtained by the trial and error process. The value of δ2 is such that δ1 < δ2 < δmax.
i.e.,
Let us begin with δ2 = 1.57 rad (approximately the middle point)
The approximate value of δ2 = 1.585 rad = 90.82°
There is a need to solve the swing equation for δ as a function of time in order to know the critical clearing time by the numerical technique. The equal-area approach enables us to calculate the critical clearing angle alone.
The evaluation of power system stability can be made effective by solving the swing equation for critical clearing time. This data is used in the design and selection of circuit breakers.
There are various methods available for solving swing equation, including the powerful Range-Kutta method. However, we shall illustrate the conventional and approximate method known as the point-by-point method, which is well-tried and prevalent.
We shall discuss the point-by-point method for one machine connected to the infinite bus bar. The procedure is however general, and can be applied to every machine in a multi-machine system.
Consider the swing equation
where,
The solution of δ(t) is obtained at discrete intervals of time with the interval spread of Δt remaining uniform throughout. The change in accelerating power which is a continuous function of time is described as follows:
In Figure 9.20(b), the numbering on axis refers to the end of intervals. At the end of the (n − 1)th interval, the acceleration power is
Fig 9.20(a-c) Plot of Acceleration, Speed and Rotor Angle: Point-by-Point Method
where δn−1 has been previously calculated.
The change in velocity ( caused by Pa(n−1), assumed to be constant over Δt from is given as
The change in δ during the (n − 1)th interval is
and during the nth interval
Subtracting Equation (9.26) from Equation (9.27) and using Equation (9.25), we get
Using this, we can write
The process of computation is now repeated for Pa(n), Δδn+1 and δn+1.
The time solution in discrete form is worked out for the required length of time, which is normally 0.5 seconds. The solution for the continuous form is obtained by drawing a smooth curve through discrete values as shown in Figure 9.20(c). The solution can be obtained with greater accuracy by reducing the time duration of intervals.
The occurrence or removal of a fault or the initiation of any switching event causes a discontinuity in the accelerating power Pa. If such a discontinuity occurs at the beginning of an interval, then the average of the values of Pa before and after the discontinuity must be used. Thus, for calculating the increment angle occurring during the first interval after a fault is applied, at t = 0 Equation (9.26) becomes,
where Pao+ is the accelerating power immediately after occurrence of the fault. The system is in steady state just before the occurrence of the fault so that Pao− = 0 and δ0 is a known value. If the fault is cleared at the beginning of the nth interval, for calculating this interval, one has to use for Pa(n−1) the value is the accelerating power immediately after clearing the fault. If the discontinuity occurs at the middle of the interval, a special procedure is required.
The increment of angle during such an interval is calculated, as usual, from the value of Pa at the beginning of the interval.
The procedure of calculating the solution of a swing equation is illustrated in following example.
A power system is shown in Figure 9.21
Fig 9.21 Power System for Example 9.5
Consider the following data
The generator is operating stably and supplying 50 MW power to an infinite bus via two transmission lines. Now, a three-phase symmetrical fault occurs at the middle of Line-2.
Solution:
Taking the rating of the equipment as base, for base MVA = 50, G = 1.0 p.u
Before fault:
Transfer reactance X = 0.4 p.u
Under steady-state:
During fault:
Transfer reactance X = 1.0 p.u
Post-fault:
Transfer reactance X = 0.6 p.u
Taking Δt = 0.05 seconds,
(a) Sustained fault:
A discontinuity exists at t = 0. Therefore, the average value of Pa used at
All the calculated values are tabulated in Table 9.2.
Table 9.2 Calculated δ values for sustained fault
A sample calculation at t = 0.1 second is given below.
Sample calculation:
The swing curve is plotted as in Figure 9.22.
Fig 9.22 Swing Curve for Sustained Fault
Table 9.3 Calculated δ values when the fault is cleared in 0.1 second
It is evident that the system is unstable.
(b) Fault cleared in 0.1 second:
The swing curve till 0.05 second is the same as that for a sustained fault. As the fault is cleared, Pm changes from 1.05 p.u at t = 0.10− to 1.75 p.u at t = 0.10+. Since the discontinuity occurs at the beginning of an interval, it is required to calculate the average value of Pa at t = 0.1 second and use this value in computing Δδ at this time. The procedure for computing the values remains the same as before.
Fig 9.23 Swing Curve for a Fault Cleared in 0.1 Second
Through tabulated results it can be concluded that the system is stable.
(c)
Using the equation,
The following methods can be used to improve transient stability:
It is important to note that the steady-state stability limit is always higher than the transient stability limit. Systems having higher steady-state stability limits are generally guaranteed for better transient stability. However, though inertia of the machine plays a vital role in transient stability, the converse is not true. By improving steady-state power limit, it can be seen in the p-δ curve that the rotor can swing in such a way that it can attain higher accelerating and decelerating areas. With this, transient stability can be improved. The value of Pmax in the p-δ curve is directly proportional to the internal voltage E of the machine. An increase in voltage increases the stability limit.
A heavy-weight machine has higher inertia and is more stable than a light-weight machine. This can be verified through the swing equation as:
If the machine has a higher inertia constant M, then during the transient period the rotor cannot swing for higher δ values. Generally a salient pole machine swings for lower load angles and is preferred over cylindrical rotor generators. The present practice of generating higher power with larger number of small machines is not recommended from the stability point of view.
The instability of a system is mainly due to excess kinetic energy stored in the rotating mass during disturbance. The problem can be avoided if the prime mover (turbine) output is quickly adjusted. This requires quick valve opening and closing action of the speed-governing system. This method is quite difficult to be implemented with conventional mechanical governors since they are too slow to respond on account of their high time constants. Electronically operated governors may be suggested for this purpose.
Whenever a fault occurs in a system, reactive power demand increases while there is a reduction in active power generation. Reduction in active power is mainly due to a rapid dip in terminal voltage as the generator experiences demagnetization armature reaction. Fast-field excitation systems quickly respond to the situation and improve the electric power output of generator, reducing the acceleration of the rotor during the disturbance period. Thus exciters help to improve the stability of the system.
As stated earlier, systems having better steady-state stability margins are guaranteed for better transient stability limits. By reducing transfer reactance, steady-state power limit can be improved. Reduction in transfer reactance can be achieved by:
As seen in Section 9.1, if the circuit breaker clears the fault before the critical clearing time, the system can maintain transient stability.
Most of the faults that occur in a system are temporary in nature. Auto re-closing circuit breakers connect the faulted lines back into service after the fault has disappeared in the system. This improves the power transfer capability, and thereby the stability of the system.
A majority of faults occurring in a system are of the single-line to ground type. If the circuit breaker is equipped with single-pole switching facility, the faulted single phase can be isolated and switched off. Power generation cannot be zero in this case and hence the stability improves. However, prolonged operation of generator with less number of phases is not advisable. Necessary precautions should be taken to counter this problem.
When a fault occurs in a generator, breaking resistors are automatically inserted across the generator terminals. The generator continues to generate power treating these resistors as load. The imbalance between mechanical input and power output is reduced, and hence the system shall be able to maintain stability.
the use of automatic enclosing circuit breakers improve system stability.
(b) Derive the formula used in the above problem.
Pre-fault condition: p = 2 sin δ
During fault condition: When B3, B4 remain closed: p = 0.2 sin δ After B3, B4 open: p = 1.5 sin δ
Calculate the critical angle δ before which breakers B3 and B4 must open so that synchronism is not lost. Also show this on a P − δ diagram.
[GATE 1991 Q.No. 8]
[GATE 1993 Q.No. 3]
[GATE 1995 Q.No. 1]
[GATE 1996 Q.No. 13]
[GATE 1997 Q.No. 4]
[GATE 1997 Q.No. 5]
[GATE 1998 Q.No. 7]
[GATE 1998 Q.No. 12]
[GATE 2000 Q.No. 14]
[GATE 2001 Q.No. 13]
x′ = 0.1p.u, E′ = 1.0p.u, H = 5MJ/MVA, mechanical power Pm = 0.0p.u, ωB = 2π × 50 rad/sec. All quantities are expressed on a common base.
[GATE 2002 Q.No. 10]
The generator is initially running on open circuit with the frequency of the open circuit voltage slightly higher than that of the infinite bus. If at the instant of switch closure δ = 0 and ω = dδ/dt = ωinit, compute the maximum value of ωinit so that the generator pulls into synchronism.
Hint: Use the equation
[GATE 2003 Q.No. 15]
[GATE 2004 Q.No. 14]
(A) The initial accelerating power (in p.u) will be
[GATE 2006 Q.No. 13]
[GATE 2006 Q.No. 14]
The synchronous generator transfers 1.0 per unit of power to the infinite bus. Critical clearing time of circuit breaker is 0.28 s. If another identical synchronous generator is connected in parallel to the existing generator and each generator is scheduled to supply 0.5 per unit of power. Then the critical clearing time of the circuit breaker will
[GATE 2008 Q.No. 53]