If the fault involves only one or two of the three possible phases, then the fault is said to be an unbalanced or asymmetrical fault. Due to these faults, the system loses symmetry or balanced condition. Fault calculations can be easily performed by the use of a tool known as the “symmetrical component”. Using these components unbalanced vectors can be transformed into balanced vectors, through which calculations can be performed on a single-phase basis. This makes calculations easier as seen in the case of symmetrical fault analysis.
In the year 1918, French mathematician Fortescue proposed a mathematical tool known as “symmetrical components”. According to this, a set of n-unbalanced vectors can be resolved into n sets of balanced vectors, with each set comprising of n-balanced vectors. For example, a set of 3-unbalanced vectors IR, IY and IB can be transformed into three sets of balanced vectors, with each set containing 3-balanced vectors.
As our interest is in 3-phase, let us transform the three unbalanced vectors into three sets of balanced vectors. These three sets are:
In terms of balanced sequence components, the unbalanced vectors can be written as follows:
Equation (7.1) can be written in the matrix form as:
In Equation (7.2) the matrix on the left hand side represents the three-phase unbalanced currents. On the right hand side, the first matrix corresponds to the positive sequence set, the second matrix corresponds to negative sequence components and the last, third matrix represents zero sequence in the three-phase system RYB. Suffix 1, 2 and 0 are assigned respectively to positive, negative and zero sequence components. The description of sequence components is as follows:
1) Positive sequence components
IR1, IY1 and IB1 corresponding to the respective unbalanced vectors IR, IY and IB are the balanced vectors having the same magnitude but displaced 120° apart. These components have the sequence of RYB of the original unbalanced vectors and are shown in Figure 7.1
2) Negative sequence components
IR2, IY2 and IB2 corresponding to the unbalanced vectors IR, IY and IB respectively are the balanced vectors having equal magnitudes, but displaced 120° apart. These components have the sequence exactly opposite to that of original unbalanced vectors. These components are shown in Figure 7.2.
In order to obtain the opposite sequence, the negative sequence components are rotated in the clockwise direction, in contrast to the conventional anticlockwise direction. This is shown in Figure 7.2(b): RBY, BYR and YRB are the negative sequences. The same negative sequence can be obtained when the vectors are rotated in the anticlockwise direction as shown in Figure 7.2(c), with the positions depicted differently.
Fig 7.1 (a) Original Unbalanced Vectors, (b) Positive Sequence Components
Fig 7.2 (a) Original Vectors, (b) Negative Sequence Components (Cw Direction), (cz) Negative Sequence Components (Acw Direction)
3) Zero sequence components
These components have no (zero) sequence. These components are equal in magnitude and are in phase with each other as shown in Figure 7.3.
In addition to the currents discussed earlier, voltages and powers are can also be transformed into sequence components.
Operator ‘a’ is defined as a unit vector with magnitude equal to 1 and angle 120° and is given as:
When a vector is multiplied by the operator ‘a’, the vector shifts to 120° in the anticlockwise direction without the magnitude being changed. Similarly, when it is multiplied by a2, it shifts to 240° in the anticlockwise direction.
Some important relations with operator a:
Fig 7.3 Zero Sequence Components
As sequence components have the same magnitude, the Y- and B-phase sequence components can be written in terms of R-phase.
Referring to Figure 7.1(b), and by taking IR1 as reference:
Referring to Figure 7.2(c) and by taking IR2 as reference:
As zero sequence components have no phase difference,
Rewriting Equation (7.1) and substituting the above relations,
Equation (7.4) may be represented in the matrix form as
Equation (7.5) may be rewritten with the operator A matrix.
where A is the operator A matrix. Similarly the voltages can be written as:
Note: For the given digital vectors, the sequence components can be obtained as:
where the inverse of the operator matrix [A] is
Let the three-phase currents be Determine the sequence components. Assume the sequence is RYB.
Solution:
The three phase currents are balanced. Using Equation (7.8b)
Using relations on operator a,
From the above,
Note: The above numerical example illustrates that in the balanced system only positive sequence currents are present.
Let the three-phase currents be The phase sequence is RYB. Find the sequence components.
Solution:
On simplification,
Determine the neutral current in the star, neutral grounded system from the given symmetrical components
Solution:
The impedance offered by the circuit component to the flow of positive sequence current is known as positive sequence impedance. Similarly, the negative and zero sequence impedances can be defined.
A summary of the experimental results of sequence impedances is presented below.
a) Generator
Positive sequence impedance
Z1 = jX″d (if the sub-transient state of fault is of interest)
= jX′ d (if the transient state fault is of interest)
= jXd (if the steady-state value of fault is of interest)
Negative sequence impedance
The negative sequence impedance offered by the generator is generally written as:
The zero sequence impedance of the generator is usually much smaller than Z1 and Z2 of values. Let Zg0 is be the zero sequence impedance of the generator. Then, the numerical values of the generator follow the relation:
b) Transformer and Transmission line
These two are said to be static devices. Since phase sequence has no effect on their operation, positive and negative sequence impedance and negative impedance are exactly be the same. For these devices, the relation between the sequence impedances is given as:
Consider a fully transposed 3-phase transmission line, having self reactance of Xs and Xm.
Solution:
Consider the transposed transmission as shown in Figure 7.4
Let Xs = Self reactance of each line
Xm = Mutual reactance between any two lines
Fig 7.4 Power System Network of Example 7.4
Voltage drop across each line is due to self and mutual reactance and is given by:
In the matrix form, the above equations can be written as:
the voltage drop and current in terms of sequence components can be written as
The voltage drop of sequence components can be obtained by multiplying sequence currents with sequence impedances. Therefore, from the above equations the sequence impedance matrix is:
On simplification of the above equation, the sequence impedance can be obtained as
where is
Note: Sequence impedance and sequence network are mutually disjoint as evident from the observation that the off-diagonal terms are zeros in Equation (7.10).
A single-phase per-unit equivalent reactance network is sufficient to couple three-phase fault analysis. This makes three-phase fault analysis simple and easier. The question of present interest is:
Can we complete unbalanced fault analysis on a single-phase basis?
The answer to this question is yes because of the use of symmetrical components in unbalanced fault analysis. The method of performing unbalanced fault analysis on a single-phase basis is presented below.
Consider the unbalanced current described by Equation (7.5)
The equation explains that unbalanced currents can be determined, once the three sequence currents are known. The three sequences IR0, IR1, IR2 are the components of R-phase currents IR. IR1 can be obtained through the positive sequence network containing positive sequence component voltages and impedance. In a similar manner the negative and zero sequence currents can also be obtained through negative and zero sequence networks. These three networks are mutually disjoint. Hence, we need to convert the given single-line diagram of the power system into three mutually disjoint sequence networks for the purpose of determining the three sequence currents. Once the sequence currents are known, the fault analysis may be concluded. The following section describes the method of converting the single-line representation of a power system into three-sequence networks.
Consider the single-line diagram shown in Figure 7.5
Figure 7.1 shows a generator, transformer and transmission line. We need to convert this into three-sequence networks. We deal this problem by understanding the procedure of representing generator, transformer and transmission line individually in the three- sequence networks. Once the procedure for individual components is known, the sequence network can be easily obtained by integrating the individual elements.
Let the generator sequence impedances be known values. Zg1, Zg2 and Zg0 are the positive, negative and zero sequence impedances of the generator. In fault analysis, the generator is represented as a constant voltage source behind the reactance. As a first step the generator placed in positive, negative and zero sequence networks is represented in a similar manner as shown in Figure 7.6.
Fig 7.5 Single-Line Diagram of a Single-Power System Network
In Figure 7.6, E is the internal emf produced by the generator. The sequence currents, impedances and voltages are also indicated in the figure. In the second step, we verify two aspects:
Fig 7.6 Generator Representation in Three-Sequence Networks
Verification of the above aspects results in modification of the generator representation in the three-sequence networks.
For a given direction of rotation of the rotor, the generator sets up emfs in the three phases with a phase sequence of RYB. As the positive sequence of voltages is also RYB, there is no problem for the generator to produce positive sequence voltages. Hence, the generator can be represented as a voltage source in the positive sequence network. To produce negative sequence voltages, the generator rotor has to rotate in the opposite direction.
A single rotor cannot rotate simultaneously in both the directions. Thus, a generator cannot generate negative sequence voltages. Hence it should not be shown as a voltage source in the negative sequence network. Finally, when the rotor starts rotating, it sets up a sequence. The zero-sequence voltages have no sequence. Therefore, the generator should generate zero-sequence voltages under still condition of the rotor. As this is not possible, it can be concluded that the generator should not be shown as a voltage source in a zero-sequence network.
Discussion on the effect of neutral grounding in generator representation
The following discussion is also valid for negative sequence network.
Let the generator neutral current In be resolved into components as: In = In1 + In2 + In0 where In1, In2 and In0 are the sum of positive, negative and zero sequence current components of R, Y and B phases as:
Fig 7.7 Generator Neutral Condition in the Positive Sequence Network
In Figure 7.3, the algebraic sum of currents leaving junction N is IR1 + IY1 + IB1, which is always zero. Since positive sequence currents are balanced and have a 120° phase shift,
Let the switch S in Figure 7.3 be open. That is, the generator neutral is ungrounded. For this condition, the current entering into junction N (i.e. In1) is zero and Kirchhoff's current law (KCL) is satisfied. Hence, there is no problem for the flow of positive sequence currents when the neutral is in open condition. Now, when the neutral is solidly grounded a current of In1 can flow through it. But as In1 = IR1 + IY1 + IB1 = 0, the sum of incoming currents is zero and KCL is satisfied. However, if the neutral is reactance grounded with Zn, the value of In1 cannot be limited to zero current. It can therefore be concluded that neutral grounding has no effect on the representation of a generator in positive and negative sequence networks, and that the condition of the neutral need not be verified.
Zero sequence Network
Let the generator neutral be ungrounded. Referring to Figure 7.8(a), the incoming current into junction N is zero, whereas the algebraic sum of outgoing currents is IR0 + IY0 + IB0 = 3 × IR0. In this ground neutral condition, KCL is not satisfied and therefore such currents do not exist. This effect can be represented as an open circuit between neutral (ZPB) and junction N as shown in Figure 7.8(b).
Fig 7.8(a) Generator Neutral Condition in the Zero-Sequence Network
Fig 7.8(b) Neutral Ungrounded Condition of the Generator
Next, let the generator neutral be grounded through an impedance Zn. In this condition, the circuit is closed, and incoming current to junction N can flow through it. The value of incoming current is Ino = 3IR0, and as the sum of outgoing current is also equal to 3IR0, KCL is satisfied. Therefore such currents do exist.
Due to flow of 3IR0 current into neutral, a voltage drop of 3IR0 Zn takes place. This raises the potential of neutral from zero to 3IR0 Zn. Now the zero potential point (ZPB) shifts down from neutral to the ground. Referring to Figure 7.8(b), the total voltage drop from ZPB to Bus-1 is:
where E = 0 in this case.
Let us consider a single-phase current component IR0 flowing into terminals. Equation (7.6) can be rewritten to consider this effect as:
Hence Zn is multiplied by 3 to get voltage drop 3IR0 Zn. The zero-sequence network of the generator is shown in Figure 7.8(d).
Fig 7.8(c) Neutral Grounded Condition of the Generator
Fig 7.8(d) Generator Representation in the Zero-Sequence Network
In Figure 7.8(d), the circuit component 3Zn can be replaced with:
Summary of generator representation
Generator representation in the three sequence networks is summarized in Figure 7.9
Fig 7.9. Generator Representation in the Three Sequence Networks
where, Z0 in the Equation (7.10) is
Power transformer in symmetrical fault analysis is represented as a series impedance element, provided per unit values are considered. Referring to Figure 7.1, the power transformer is connected between buses 1 and 2. Let the transformer be connected as a series impedance element in the three sequence networks, as in symmetrical fault analysis. We need to verify two aspects before finalizing this representation.
Verification of the above, results in modifications to the representation of the transformer in the there sequence networks. First, we verify the effect of the type of windings on transformer representations. The following explanation is valid for positive and negative sequence networks. Consider Figure 7.10, in which a star (ungrounded neutral)-delta transformer is connected between buses 1 and 2.
Let the positive sequence current of the three phases come through the generation terminals before Bus-1. The transformer can be shown as a series reactance element, if this current appears beyond Bus-2. Positive sequence currents can flow into the star winding, provided KCL is satisfied at junction N. The sum of incoming currents of the balanced positive sequence currents is IR1 + IY1 + IB1 = 0. Similarly, the current leaving N is also zero (since N is not grounded). This verifies that KCL is valid and therefore it can be concluded such currents do exist. The flow of sequence currents into the primary winding causes the magnetic core of the power transformer to get magnetized. The magnetized core establishes secondary currents in the delta-connected winding. The line current in the delta winding is the vector difference of the two phase currents, and it is not equal to zero due to the 120° phase difference. The line current flows beyond Bus-2 and this proves that the transformer acts as a series impedance element to pass positive sequence currents from Bus-1 (generator side) to Bus-2 (transmission line side). The currents in other types of transformer windings can be verified in the same way.
Fig 7.10 Star-Delta Power Transformer Connected Between Buses 1 and 2
Summarizing the above, it can be stated that a transformer can be simply represented as series impedance on a reactance element without verifying the type of transformer winding or the condition of the neutral. Moreover, as Z1 = Z2 for a transformer, both positive and negative sequence networks appear quite similar.
The zero-sequence equivalent circuit of a transformer is not like the others. It is influenced by the type of winding and the condition of the neutral. We shall consider two cases and leave the third to the reader as an exercise.
Case-1: Let the transformer primary be star connected (neutral grounded) and the secondary be delta connected.
Fig 7.11(a) A Star-Delta Transformer for a Zero-Sequence Network
Consider Figure 7.11(a). The transformer is connected between buses 1 and 2. Let the zero-sequence current flow out from generator terminals. These currents can flow into primary winding, provided KCL is satisfied at junction N. The sum of incoming currents to junction N is IR0 + IY0 + IB0 = 3IR0 and the out flowing current is IN0 = 3IR0. This verifies that KCL is valid and that such currents do exist. These primary currents induce secondary currents in the delta connected windings (phases). But the line current on the delta side is zero as the difference between any two phase currents, say for example, IR0 – IY0 = 0. Therefore currents can appear up to the secondary side and return. This is shown in Figure 7.11(b).
Fig 7.11(b) A Star-Delta Transformer Representation in the Zero Sequence Network
Case-2: Now consider a star-star transformer. The neutral on both sides are grounded solidly. This is shown in Figure 7.12(a).
Fig 7.12(a) A Star-Star Transformer for a Zero Sequence Network
In this case, KCL is satisfied at the junctions on both sides and current can pass from Bus-1 to Bus-2 through the power transformer. In other words, the transformer can act like a series impedance element as shown in Figure 7.12(b).
A current of 3IR0 at the neutral produces a drop of 3IR0 Zn. This effect can be shown in the network by adding 3Zn to Z0 of the transformer.
Switch diagram for the representation of transformer in a zero-sequence network
The switch diagram shown in Figure 7.13 can be used to represent a transformer in the zero-sequence network. The circuit consists of two series switches (1 and 2) and two shunt switches (11 and 21). 1–11 corresponds to the primary and 2–21 corresponds to the secondary side of the transformer. Z0 is the zero sequence impedance of the transformer.
Fig 7.12(b) Representation of a Star-Star Transformer for a Zero Sequence Network
Fig 7.13 Switch Diagram for Representation of Transformer in the Zero-Sequence Network
Rules for using the switch diagram:
Example: Let the primary side of the transformer be delta connected and the secondary side, star connected with the neutral grounded. Then, switches 11 and 2 may be closed. Other types of connections are given in Example 7.5.
Give the zero-sequence network equivalent for the transformer connected between buses 1 and 2. Use switch diagram.
Transmission lines can be represented as series impedance elements in all the three sequence networks. Transmission lines between buses 2 and 3 may be depicted as shown in Figure 7.14. Similar representations may be made for all the three sequence networks. In Figure 7.14, Z1, Z2 and Z0 are the per unit sequence impedance of the respective networks.
Fig 7.14 Transmission Line Representation for the Three Sequence Networks
Knowledge of representation of individual components helps to convert any power system network into three-sequence networks for the calculation of fault currents in unbalanced fault analysis.
Figure 7.15 represents a simple power system. Draw its positive, negative and zero-sequence networks.
Fig 7.15 Simple Power System for Example 7. 6
Solution:
Positive sequence network
Negative sequence network
Zero-sequence network
The following are the types of unbalanced faults:
It has been mentioned in Section 7.4 that fault analysis is also carried out on a single-phase basis, similar to symmetrical fault analysis, with the difference lying in the fact that the former involves working with three-sequence networks instead of with a single network. Though this type of analysis may call for more effort, it is advantageous to work on a single-phase basis. The method of drawing the three-sequence diagram for a given power system network consisting of generators, transformers and transmission lines has also been discussed in earlier sections.
The following steps are involved in unsymmetrical fault analysis. These steps are common to all the three types of balanced faults.
Step 1: Convert the given power system network into three equivalent p. u. sequence networks.
Step 2: Look for the fault location and reduce the three-sequence networks into three Thevenin's equivalents across the fault terminal F and ZPB. Get the Thevenin's positive, negative and zero sequence impedances. Also, obtain pre-fault open circuit voltage E from the Thevenin's equivalent circuit.
Step 3: Obtain the values of sequence currents.
Step 4: Obtain the unbalanced currents using the equation:
Step 5: Obtain the sequence voltages from
where, IR1, IR2, IR0 are previously calculated and Z1, Z2, Z0 are Thevenin's equivalent impedances obtained earlier.
Step 6: Obtain phase voltages from:
This concludes the fault analysis.
Assume initially that the system is isolated from the load end. The pre-fault balanced condition of the system is:
Now, consider an SLG fault occurring at point F as shown in Figure 7.16.
Fig 7.16 SLG Fault
If is the fault current. The fault has an impedance of Zf. If the fault is a dead short-circuit, then Zf = 0 or VR.= 0 with a fault impedance of Zf. During the fault, the condition of the system is:
To complete the fault analysis, we need the relation between sequence currents and their magnitudes.
Relation between sequence currents:
From the above,
The relation between sequence currents for a SLG fault is:
i.e., all the sequence currents are equal. Now, we shall find the magnitudes of the sequence currents:
Fault voltage Vf = VR = If Zf = IRZf
In terms of sequence components,
Using Thevenin's equivalent circuits obtained across F and ZPB, the sequence voltages can be written as:
As all the sequence currents are equal,
From the above equation, the magnitude of sequence current IR1 is
Since all the sequence currents are equal,
and the fault current is: If = IR = 3IR1
Therefore,
The relations represented by Equations (7.12), (7.13) and (7.14) can be easily obtained by connecting Thevenin's equivalent sequence networks in series as shown in Figure 7.17. Further, the sequence currents may also be computed by using this series circuit.
The next step is finding the sequence voltages as:
Fig 7.17 Sequence Network Connected in Series for a SLG Fault
and three-phase voltages as:
This concludes SLG fault analysis.
Assume initially that the power system is isolated from the rest of the system, such that IR = IY = IB = 0 and that the three-phase voltages are balanced. Now, assume that a double line fault with a fault impedance of Zf has occurred across Y and B phases as shown in Figure 7.18.
Fig 7.18 LL Fault
During the fault condition of the system:
IR = 0 (due to healthy condition);
Fault current If = IY – IB (for the direction shown)
Relation between sequence currents:
The sequence currents at the fault point are:
From the above equation,
and
Therefore the relation between sequence currents for an LL fault is:
Magnitude of sequence currents:
Replacing symmetrical components for VY, VB or If (=IY) in the above equation,
Using Equation (7.16)
Substituting equations for sequence voltages,
As IR2 – IR1, the above equation modifies to:
From the above, the magnitude of IR1 is:
where E, Z1, Z2 are Thevenin's equivalent sequence network parameters.
Therefore, the relation may be given by
The fault current If = IY can be obtained as:
but
Substituting a2 – a value, the equation for If is:
and the magnitude of fault current is:
Knowing the values of sequence currents and sequence voltages, three-phase voltages may be obtained by a similar procedure as explained for SLG fault in Section 7.5.1. Sequence networks for the fault can be drawn in series opposition as shown in Figure 7.19
Fig 7.19 Sequence Networks for LL Fault
Figure 7.15 is drawn in accordance with Equation (7.18) and can be used to find and establish sequence currents.
Let the pre-fault condition of the system be: IR = IY = IB = 0 and the three-phase voltages be balanced. Now, a double line-to-ground fault occurs between Y and B phases to the ground. The fault impedance is Zf. This is shown in Figure 7.20(a).
Fig 7.20(a) LLG Fault on the System
When fault occurs, the condition of the system may be written as:
IR = 0 (due to healthy condition)
If = fault current = IY + IB
Equation (7.18) in sequence components can be written as:
From the above,
From Equation (7.18)
Replacing VY, IY, IB in terms of sequence components,
As
The above equation can be written as
During fault condition,
Substituting the above condition in Equation (7.20),
Equation (7.19, 7.21, and 7.22) can be obtained by connecting the sequence networks in parallel. This is shown in Figure 7.20(b):,
Fig 7.20(b) Connection of Sequence Networks for LLG Fault
In Figure 7.20(a), Equations (7.19, 7.21 and 7.22) can be proved.
Relation between sequence currents:
If Zf = 1 (dead short-circuit), all the sequence voltages are equal. This means all the sequence networks are connected in parallel for an LLG fault. Using Figure 7.20(a), the magnitude of sequence currents can be found as:
IR1 = Total current in the circuit
where E, Z1, Z2 and Z3 are Thevenin's equivalences of positive, negative and zero sequence networks. Using current division formula
Equations (7.24–7.26) can be used to determine sequence currents. Using these sequence currents, the fault current and sequence voltages can be obtained as:
Using the sequence voltages, all the three phase voltages can be obtained as:
This concludes LLG fault analysis.
Under balanced condition
This means that, symmetrical fault analysis requires only the positive sequence network as shown in Figure 7.21.
Fig 7.21 Three-Phase Fault
Figure 7.21 is the Thevenin's equivalent circuit obtained using positive sequence network across faulted point F and ZPB.
Summary of Faults
When the fault involves only one phase, fault current is expected to be the least. Where as, involvement of all the three phases gives rise to the highest fault current. A comparison of these two faults, when they occur on the terminals of various equipments is presented in this section. Let the sequence impedance Z1, Z2 and Z0 be pure reactances, and consider a dead short-circuit with Zf = 0. The three-phase and SLG fault currents are given by:
Case-1: Ungrounded neutral alternator
When the fault is at generator terminals with the generator neutral grounded, Z0 = ∞.
Case-2 : Solidly grounded neutral alternator
In this case, the zero-sequence reactance of the generator is X0 = Xg0 + 3Xn = Xgo (as Xn = 0 for solidly grounded neutral case)
The following relations are valid for the generator:
(for the sub-transient state)
Substituting the above relations,
From the above,
It is seen that for the solidly grounded neutral alternator, an SLG fault is more than a three-phase fault.
Case-3: Generator neutral reactance grounded
Generator neutral is grounded through reactance Xn. Xn has no effect on the magnitude of the three-phase fault, but it is designed as Substituting Xn value of the above and following the relations between sequences of the generator, the SLG fault current is:
This means, for the designed value of Xn, the SLG fault current is equal to the three-phase fault current. For different values of Xn, the relations are shown below:
Xn value | Relation |
---|---|
Case-4 Faults on Transformer / Transmission line
For the transformer and transmission lines of static devices, X0 >> X1. For this relation of reactances, a three-phase fault is always the reverse of an SLG fault.
The exact value of current during the faulty condition of a system can be obtained by superimposing pre-fault load currents on to the fault currents. The following presents the procedural steps:
An alternator rated 11 kV, 50 MVA with neutral solidly grounded has X1 = X2 = j0.1 p. u. and X0 = j0.05 p.u. It is supplying power to an 11 KVA, 25 MVA motor which has X1 = X2 = j0.1 p.u and X0 = j0.05 p.u. through a short transmission line. Line reactances are X1 = X2 = j 0.01 p.u and X0 = j0.4 p.u. All the equivalent reactances are pre-calculated on a 50 MVA, 11 KV base. The motor is drawing a power of 25 MW at 0.866 lag. The motor terminal voltage at loaded condition is 0.95 p. u. An SLG fault occurs on the phase-R of the generator. Calculate the fault current in phase-R of the generator under the given fault conditions.
Solution:
Taking the motor voltage as reference, the load current lags it by 30°.
Considering the positive sequence network of the system
Fig 7.22(a) Positive Sequence Network
Terminal voltage of generator = V
Fig 7.22(b) shows the interconnection of sequence networks for an SLG fault
Fig 7.22(b) Interconnection of Sequence Networks for an SLG Fault
The sequence components of the fault are
The component of positive sequence fault current flowing through the generator is
As the load current is a fully positive sequence, the total positive sequence component current during the fault is:
Negative sequence component current through generator (0.018 – j3.345) p.u. Zero sequence component current through the generator
The total current through Generator is
Figure 7.23 shows a simple power system network. Draw the positive, negative and zero sequence networks.
Fig 7.23 A Simple Power System Network
The numerical data of various components in the power system is given as under: (all values are in p. u.)
Generator G1: 50 MVA, 11 KV, X1 = X2 = 0.2; X0 = 0.01;
Generator G2: 100 MVA, 11 KV, X1 = X2 = 0.25; X0 = 0.02;
Transformer T1: 50 MVA, 11/132 KV, X1 = X2 = 0.2; X0 = 0.4
Transformer T2: 100 MVA, 11/132 KV, X1 = X2 = 0.1; X0 = 0.1
132 KV Line: 100 MVA, 132 KV, X1 = X2 = 0.1; X0 = 0.25
Solution:
Common base MVA = 100 MVA;
Base voltage on LT side = 11 KV
Base voltage on HT side = 132 KV
Equipment per unit sequence impedances and common base values are completed below.
132 KV Line: X1 = X2 = 0.1; X0 = 0.25 p.u
G2 (neutral-ground reactance)
The pre-fault induced emf of G1 and G2 are assumed as 1 p. u.
a) Positive sequence network:
b) Negative sequence network:
For the network in Example 7.8, simulate fault on Bus-3. Obtain Thevenin's equivalent positive, negative and zero sequence networks.
Solution:
Thevenin's equivalent circuit of positive, negative and zero sequence networks across Bus-3 and ZPB are obtained as follows:
a) Thevenin's equivalent positive and negative sequence networks:
b) Thevenin's equivalent zero-sequence network
The part of the network on the left hand side of Bus-3 is not considered due to discontinuity at Bus-2.
A single line-to-ground fault occurs at Bus-3 of the network of Example 7.8; using Thevenin's equivalent sequence networks obtained in Example 7.9, determine the faulty phase and healthy phase:
a) Currents
b) Phase voltages
c) Line-to-line voltages
Solution:
(a) Thevenin's equivalent sequence reactance are obtained in Example 7.7. X1 = X2 = j0.252 p. u, X0 = j0.1 p. u.
Sequence currents are equal for an LG fault
Assuming a fault in an R-phase
The magnitude of SLG fault current
Current in all phases
(b) Sequence voltages at the fault point are:
The three-phase voltage (phase) values are:
Thus, line-to-neutral voltages at the fault point are:
A synchronous generator rated 3-phase 11 KV, 100 MVA has X1 = X2 = j0.1 p.u and X0 = j0.04 p.u. Determine the fault current and line-to-line voltages during the fault condition: (a) if a single line-to-ground (SLG) fault occurs on the generator terminals, (b) if the generator neutral is solidly grounded, (c) if the generator is operating at no-load and rated voltage prior to the fault.
Solution:
It is usual practice for the rating of the equipment to be taken as base values.
For an SLG fault
Sequence voltages at fault point are:
Phase voltages at fault point are:
Line-to-line voltages
since, the generator line-to-neutral voltage is taken as 1 p.u.
Consider the power system shown in Figure 7.24.
Fig 7.24 Power System Network of Example 7.12
An SLG fault occurs at Bus-2 at the far end of the line. Consider the numerical data:
Determine the fault current magnitude:
Let Base MVA = 50 MVA
Base voltage = 33 KV
Line sequence reactance in p.u
Consider the power system of Example 7.12.
Consider the synchronous generator of Example 7.11. Determine the fault current and line-to-line voltages if a double line fault occurs on the generator terminals.
Solution:
For LL fault,
Now, the line current is:
For LL fault,
Line-to-neutral phase voltages are:
While calculating the sequence [1 + a + a2 = 0] the current and line-to-neutral voltage (phase voltage) are taken as 1 p.u
Line-to-line voltages
Consider the synchronous generator of Example 7.11. Determine the fault current and line-to-line voltages if a double line-to-ground fault occurs at the generator terminals
Solution:
Positive, negative and zero sequence networks are connected in parallel as shown in Figure 7.25.
Fig 7.25 Thevenin's Equivalent Sequence Networks Connected in Parallel for an LLG Fault
From the figure,
Using the current division formula,
The line currents in R, Y and B are:
For an LLG fault, all the sequence voltages are equal.
Line-to-neutral voltages of the generator are:
Since 1 p.u voltage KV
Line voltages
Consider the power system of Example 7.8 and Thevenin's equivalent sequence networks obtained in Example 7.9. Determine the magnitude of fault current if a double line (LL) fault occurs on Bus-3.
Solution:
Thevenin's equivalent sequence networks for LL fault are connected as shown in Figure 7.26
Fig 7.26 Sequence Networks for Double Line Fault
Considering data E = 1 X1 = X2 = 0.252 p.u
Sequence voltages
Phase voltages at the location of fault are:
Line voltages at the location of fault are:
Since sequence currents are computed by considering line-to-neutral voltage as 1 p. u, the base voltage taken in the problem is:
Consider the power system of Example 7.8 and Thevenin's equivalent sequence networks obtained in Example 7.9. Determine the magnitude of fault current if a double line- to-ground fault (LLG) occurs on Bus-3. Assume fault impedance as zero.
Solution:
All the three sequence networks are connected in parallel for an LLG fault as shown in Figure 7.27.
Fig 7.27 Sequence Networks Connected in Parallel for an LLG Fault
Line current in the three phases are:
Base current = 437.4 Amp (ref Example 7.10)
Fault current:
Sequence voltages
Phase voltages at fault location
Line voltages at fault location
While calculating sequence voltages, phase voltage E is taken as 1 p.u.
Therefore, 1 p.u voltage at fault location
Consider the power system of Example 7.7 and Thevenin's equivalent sequence networks obtained in Example 7.9. Determine the magnitude of fault current if a symmetrical three-phase fault current occurs on Bus-3.
Solution:
For symmetrical faults, only positive sequence network is considered.
Fault currents in lines are:
Line voltages at the fault location
Since VR1 = VR2 = VR0 = 0 all line voltages are zero at the fault location.
Three faults simulated on a power system give the following results:
The base values at the fault location are: 100 MVA, 132 KV. Find the p. u values of all sequence impedances of Thevenin's equivalent networks.
Solution:
A three-phase generator noted 10 MVA, 11 KV has a solidly grounded neutral. The sequence impedances of the alternator are: Z1 = j 0.4; Z2 = j 0.35 and Z0 = j 0.05 p.u. The resistances are negligible. What value of (a) reactance and (b) resistance must be placed in general neutral for a single line-to-ground fault of zero fault impedance to the rated line current?
Solution:
Taking equipment rated values as base, the generator rated current:
Base impedance
1 p.u current = 524.87 A
Consider the generator of Example 7.20. What value of reactance is needed to connect from neutral to ground, such that the three-phase fault and SLG fault currents are equal?
Solution:
Solving the above,
A three-phase 50 MVA, 11 KV star-connected alternator neutral is grounded through a 30% pure resistor. It has X1 = X2 = 20% and X0 = 5% when the generator is unloaded. A single line-to-ground fault occurs on the R-terminal through a fault impedance of 0.1 + j0 ohms. Determine fault currents in all the phases and also the earth fault current.
Solution:
Taking equipment rating as base values,
Symmetrical fault analysis and unsymmetrical fault analysis for a small power system can be carried out by the procedure discussed in Chapter 6. However, for large power systems obtaining Thevenin's equivalent circuit is quite tedious and difficult. Fault analysis for large interconnected power systems can be easily performed by using the bus impedance matrix. The reader should refer to Chapter 3 to understand the algorithm for a bus impedance matrix (ZBus). The three sequence networks are first converted into graphs using the building algorithm for ZBus and the three different sequences of bus impedance machines are initially given names Z1,Bus, Z2,Bus and Z0,Bus. For an n-bus power system the size of these machines are (n × n).
The following mutations are used in the analysis.
Let,
V1,Bus = Positive sequence bus voltage matrix of dimension (n × 1), for Kth bus VK1
V2,Bus = Negative sequence bus voltage matrix of dimension (n × 1), for Kth bus VK2
V0,Bus = Zero-sequence bus voltage matrix of dimension (n × 1), for Kth bus VK0
Similarly, buses I1, I2, and I0 represent three sequence currents with general entries for the Kth bus as IK1, IK2 and IK0 respectively.
EBus = Pre-fault voltage matrix of dimension (n × 1), all elements being equal to p. u
Matrices representing sequence voltages can be obtained from:
Analysis of all types of faults using ZBus
Short circuit analysis can be carried out by using Equations (7.28–7.30).
Assume that a fault has occurred at Bus K in an n-bus power system. Initially, the system is working under no fault condition.
For a three-phase fault, a symmetrical fault corresponding to negative and zero- sequence components does not exist except in the case of positive sequence machines.
Now, the Kth entry of V1,Bus is:
All bus currents except the Kth bus are zero,
Vk1 at the fault location can also be written as,
i.e, the Kth bus voltage is potentially higher by IK1 Zf, where Zf is the fault impedance from Equations (7.31) and (7.32). The symmetrical fault current is
The healthy bus voltages are:
For an SLG fault, all sequence currents are equal.
All sequence currents at other healthy buses are zeros
The K 15 bus voltage is potentially higher than ZPB by
The sequence voltages are:
Substituting Equations (7.36–7.38) in (7.35) we get,
The result of Equation (7.39) can be substituted in Equations (7.36)–(7.38) to evaluate sequence voltages.
SLG fault current at the Kth bus is:
The sequence voltages of other healthy buses can be computed as:
and i15 bus voltage is:
For an LL fault,
In the positive and negative sequence methods, the lines are connected in series opposition and the following equations can be used
Using Equations (7.36) — (7.38), Equation (7.46) is modified as:
From the above equation,
Now, the fault current in the Y-phase of Kth bus is:
The sequence voltages of other healthy buses can be computed as:
I1k is computed using Equation (7.47)
For an LLG fault,
From the equivalent circuit drawn for an LLG fault, we can write:
From Equations (7.36–7.38)
Using Equation (7.53),
Substituting Equations (7.54 to 7.55) in Equation (7.52),
The denominator in the Equation (7.57) can be represented as Z. Substituting Equation (7.57) in Equations (7.54) — (7.56)
where Z = Z1kk(Z2kk + Z0kk + 3Zf) + 22kk(Z0kk + 32f)
Using Equations (7.58) — (7.60), the sequence currents can be determined through which the LLG fault can be computed as:
If1,LLG = Y-phase current of Kth bus
+ B-phase current of Kth bus
The Y and B phase currents can be calculated using sequence currents of Ik
Other healthy bus voltages can be computed as given below:
for i = 1, 2,…, n, i ≠ k.
Ik0 Ik1 and Ik2 can be computed by using Equations (7.54 — 7.56)
A single line-to-ground fault on phase-R occurs on Bus-2 in the system of Figure 7.28(a)
Fig 7.28(a) A Two-Bus Power System
Compute the following in per unit
Bus impedance matrix of positive, negative and zero-sequence networks
Fault current and healthy phase voltages
Solution:
The passive positive and negative sequence networks are represented by the circuit shown in Figure Ex 7.28(b) and zero sequence network in Figure 7.28(c).
Fig 7.28(b) Positive and Negative Passive Sequence Network
Fig 7.28(c) Passive Zero-Sequence Network
a) Formation of positive and negative sequence bus impedance matrices.
Step-1: Adding element from Reference to Bus-1,
Step-2: Adding element from Bus-2 to Bus-1,
Step-3: Adding element from Bus-2 to Reference,
Formation of ZBus
With reference to Figure 7.23 (b), Z, Bus is obtained below
Step-1: Adding element from Reference bus to Bus-1
Step-2: Adding element from Bus-1 to Bus-2
Step-3: Adding element from Bus-2 to Reference
(b) An SLG fault occurs on Bus-2. Using Equation (7.39), the sequence currents are (zf = zn = 0):
The line currents at Bus-2 are
Using Equations 7.41–7.43, the sequence voltage of healthy Bus-1 can be competed.
and V1 = V10 + V11 + V12
= 0.419 p.u (Ans)
Repeat the Example 7.23, if a 3-phase fault occurs on Bus-2.
Solution:
Using Equation (7.33),
For 3 fault, I20 and I20 are absent.
The line currents at faulted Bus-2 are:
Using Equation (7.34), the healthy Bus-1 voltages can be computed.
For a symmetrical fault V12 = V10 = 0
The line-to-neutral voltages at Bus-1 are:
Repeat the Example 7.23, if a double line fault occurs at Bus-2.
Solution:
Using Equation (7.47)
Line currents at the faulted Bus-2 are:
From the above,
The sequence voltages of healthy Bus-1 can be computed by using Equations 7.49 and 7.50
Phase-to-neutral voltage at Bus-1 is:
The positive sequence bus impedance matrix of a 4-Bus power system network is given below:
Calculate the fault current, if a symmetrical fault occurs on Bus-2.
Solution:
Using Equation (7.33),
The line currents in R, Y and B Phases at Bus-2 are:
Consider the data given in Example 7.26 for the 4-bus system. The positive and negative bus impedance matrices are the same. Find the magnitude of fault current if an LL fault occurs at Bus-3.
Solution:
Using Equation (7.47)
using Eq.(7.48);
If the base current is known, the magnitude of fault current in amperes can bedetermined.
(b) Explain the concept of sequence impedance of a 3-ø star connected, rotating load whose neutral is grounded through some impedance and draw its sequence impedance networks
(b) Obtain the symmetrical components of the following set of unbalanced currents:
(b) A 3-ø, 11 KV, 25 MVA Generator with X0 = 0.05 per unit and X1 = 0.2 per unit is grounded through a reactance of 0.3 Ω. Calculate the fault current for a double line-to-ground fault. Also calculate the terminal voltage of the faulted phase.
(b) A 30 MVA, 11 KV, 3-ø synchronous generator has a direct sub-transient reactance of 0.25 per unit. The negative and zero-sequence reactances are 0.35 and 0.1 per unit respectively. The neutral of the generator is solidly grounded. Determine the sub-transient current in the generator and the line-to-line voltages for sub-transient conditions when a single line-to-ground fault occurs at the generator terminals with the generator operating unloaded at rated voltage.
(b) A 3-ø, 11KV, 25MVA generator with X0 = 0.05 p.u., X1 = 0.2 p.u. is grounded through a reactance of 0.3. Calculate the fault current for a single line-to-ground fault. Also calculate the terminal voltage of the faulted phase with respect to the ground.
(b) A 3-ø, 11 KV, 25 MVA generator with X0 = 0.05 p.u., X1 = 0.2 p.u. is grounded through a reactance of 0.3. Determine the ratio of fault current of double line-to-ground fault to the single line-to-ground fault, considering one fault at a time.
(c) Derive the formulas used in the above problem
(b) Explain the concept of sequence impedances of a 3-ø star-connected rotating load whose neutral is grounded through some impedance, and draw its sequence impedance networks.
(b) Obtain the expressions for sequence impedances of a 3-ø, 3-wire transposed transmission line. Also draw the sequence impedance networks. Assume that the transmission line is having mutual impedance from phase to phase.
(a) A 3-ø alternator is supplying power to the star-connected load through a feeder. The alternator per phase impedance is equal to ZS and the load impedances are ZR, ZY and ZB in R-, Y- and B-phases respectively. Neglect the feeder impedance. Derive the expression for phase currents and phase voltages at the load end, when there is an open conductor fault at the R-phase. Assume both neutrals are solidly grounded.
(b) A 3-ø, 400 V, 1 MVA alternator has per-phase reactance of 3 Ω and negligible resistance supplying power to a star-connected load having reactances 10 Ω, 20 Ω, and 15 Ω in R-, Y-, and B-phases respectively. Calculate the phase currents and phase voltages at the load side, when an open conductor fault occurs at the R-phase of the feeder. Assume that both neutrals are solidly grounded.
IR = (12 + j6); IY = (12 - j12) A
IB = (-15 + j10) A
The phase sequence is RYB. Calculate the zero, positive and negative sequence components of the currents.
[GATE 1995]
[GATE 1996]
The zero-sequence driving point reactance of the Node 3 is
[GATE 1998]
[GATE 2002]
[GATE 2003]
The fault that has occurred is
If a 3-Phase fault occurs at Bus-2, the p.u fault current in each phase is
The p.u X1 and X2 of the machine are:
Ia0 = j2.37p.u.
Ia1 = j3.05p.u
Ia2 = j0.68 p.u.
Va0 = Va1 = Va2 = 0.237 p.u.
The fault that has occurred is_____________.
[GATE 1991 Q.No.5]
A single line diagram of a power system is shown in figure, where the sequence reactances of generator (G), synchronous motor (M) and transformers (T1,T2) are given in per unit. The neutrals of the generator and transformers are solidly grounded. The motor neutral is grounded through a reactance Xn = 0.05 per unit. Draw the positive, negative and zero sequence networks with reactance values in per unit on a 100 MVA, 13.8 kV base in the zone of the generator. The pre-fault voltage is 1.05 < 20 per unit.
Calculate the per unit fault current for a three-phase to ground fault at bus ‘d’. The system data are as follows:
G - 100 MVA; 13.8 kV; X1 = 0.15; X2 = 0.17; X0 = 0.05
T1,T2-120 MVA; 13.8 kV/138 kV∆/Y; X=0.12
M - 100 MVA; 13.8 kV; X1 = 0.2, X2 = 0.21, X0= 0.1; Xn = 0.05
Line — X1=X2=20 ohms; X0 =60 Ohms
[GATE 1992 Q.No.7]
[GATE 1994 Q.No.1]
The parameter, on 250 MVA base, are as follows:
Generator : | X1 = X2 = 0.15 p.u, X0 = 0.1 p.u |
Transformer : | 11/220 kV, 205 MVA |
X1 = X2 = X0 = 0.12 p.u. | |
Line: | X1 = X2 = 0.25 p.u., X0 = 0.75 p.u. |
Equivalent system | X1 = X2 = X0 = 0.15 p.u.> |
[GATE 1994 Q.No.8]
[GATE 1995 Q.No.8]
X1 = 0.25 p.u; X2 = 0.35 p.u and X0 = 0.10 p.u
The neutral of the alternator is solidly grounded. Determine the alternator line currents when a double line-to-ground fault occurs on its terminals. Assume that the alternator is unloaded and is operating at rated voltage when the fault occurs.
[GATE 1995 Q.No.16]
[GATE 1996 Q.No.6]
The system data is as given in the table below:
Generator ground reactance is 0.5 p.u.
[GATE 1996 Q.No.14]
[GATE 1997 Q.No.2]
[GATE 1998 Q.No.8]
[GATE 2000 Q.No.10]
[GATE 2001 Q.No.7]
[GATE 2001 Q.No.12]
[GATE 2001 Q.No.5]
[GATE 2002 Q.No.7]
[GATE 2003 Q.No.10]
[GATE 2003 Q.No.12]
[GATE 2003 Q.No.16]
[GATE 2004 Q.No.13]
[GATE 2005 Q.No.11]
The pre-fault voltages are 1.0 p.u. at all the buses. The system was unloaded prior to the fault. A solid 3-phase fault takes place at bus 2.
[GATE 2006 Q.No.15]
[GATE 2006 Q.No.16]
An ‘a’ phase to ground fault with zero fault impedance occurs at the centre of the transmission line. Bus voltage at X and line current from X to F for the ‘a’, are given by Va volts and Ia Amperes, respectively. Then, the impedance measured by the ground distance relay located at the terminal X of line XY will be given by
[GATE 2008 Q.No.14]
Given that:
Vs1=Vs2=1.0 + j0.0pu;
The positive sequence impedance are Zs1=Zs2=0.001 + j0.01 pu and ZL =0.006 + j0.06pu.
3-phase Base MVA=100
Voltage base = 400 kV (Line to Line)
Nominal system frequency =50 Hz
The reference voltage for phase ‘a’ is defined as v(t)=Vm cos(ωt) .
A symmetrical three-phase fault occurs at centre of the line, i.e. point ‘F’ at time t0.The positive sequence impedance from source S1 to point ‘F’ equals 0.004 + j0.04pu. The waveform corresponding to phase ‘a’ fault current from bus X reveals that decaying dc offset current is negative and in magnitude at its maximum initial value. Assume that the negative sequence impedances are equal to positive sequence impedances, and the zero sequence impedances are three times positive sequence impedances.
[GATE 2008 Q.No.71]
[GATE 2008 Q.No.72]
[GATE 2008 Q.No.73]