This chapter focuses on the system stability control and relay protection of power system with large-scale wind power integrated and proposes corresponding measures. In addition, an automatic voltage control method is introduced.
Table 4.1
Rated power P (MW) | 1.5 | Stator resistance Rs (p.u.) | 0.004 |
Output voltage U (kV) | 0.69 | Stator reactance Xs (p.u.) | 0.1 |
Field reactance Xm (p.u.) | 3.5 | Rotor resistance Rr (p.u.) | 0.01 |
Rotor reactance Xr (p.u.) | 0.1 |
Table 4.2
Calculated 3-Phase Short-Circuit Current of the Main Buses in the Grid When the Northwest Grid was Integrated to Xinjiang and the Wind Farms Stopped Operation and Fully Generated the Power
No. | Name of the Short-Circuit Bus | Short-Circuit Current (kA) | Growth Rate (%) | |
Shut Down of WTGs | Start-Up of All WTGs | |||
1 | Dunhuang 750 kV substation bus | 15.41 | 21.27 | 38.03 |
2 | Jiuquan 750 kV substation bus | 17.59 | 21.23 | 20.69 |
3 | Hexi 750 kV substation bus | 22.39 | 23.96 | 7.01 |
4 | Dunhuang 330 kV substation bus | 22.96 | 40.23 | 75.22 |
5 | Jiuquan 330 kV substation bus | 27.42 | 31.55 | 15.06 |
6 | Hexi 330 kV substation bus | 27.69 | 28.39 | 2.53 |
7 | Yumenzhen 330 kV substation bus | 9.45 | 16.54 | 75.03 |
8 | Jiayuguan 330 kV substation bus | 20.84 | 24.43 | 17.23 |
Table 4.3
Calculated 3-Phase Short-Circuit Current of the Main Buses in the Grid, the Northwest Grid was Not Integrated to Xinjiang, the Wind Farms Stopped Operation, and They Fully Generated the Power
No. | Name of the Short-Circuit Bus | Short-Circuit Current (kA) | Growth Rate (%) | |
Shut Down of WTGs | Start-Up of All WTGs | |||
1 | Dunhuang 750 kV substation bus | 8.73 | 14.60 | 67.24 |
2 | Jiuquan 750 kV substation bus | 12.46 | 17.63 | 41.49 |
3 | Hexi 750 kV substation bus | 19.38 | 22.44 | 15.79 |
4 | Dunhuang 330 kV substation bus | 15.62 | 33.14 | 112.16 |
5 | Jiuquan 330 kV substation bus | 23.51 | 29.67 | 26.20 |
6 | Hexi 330 kV substation bus | 26.25 | 27.76 | 5.75 |
7 | Yumenzhen 330 kV substation bus | 8.61 | 16.23 | 88.50 |
8 | Jiayuguan 330 kV substation bus | 18.43 | 23.39 | 26.91 |
Table 4.4
Relevant Swing Mode Characteristics in Summer Minimum Mode, 2010, before the Wind Farms in Jiuquan Region Are Integrated (Not Provided with Serial Compensating Capacitors, and Not Integrated with Xinjiang)
Mode | Characteristic Root | Damping Frequency (Hz) | Damping Ratio (%) | Modal Analysis | Participant Factor |
1 | −0.206 ±j4.439 | 0.706 | 4.643 | Swing between the units of Gansu, Qinghai and the units of Shaanxi and Ningxia Units #1, #2 of Liujiaxia, Gansu = 0.00019 Unit #1, technical improved, Ningxiashi = 0.00017 | Units #1, #2 of Liujiaxia, Gansu = 1 Unit #1, technical improved, Ningxiashi = 0.47 |
2 | −0.245 ±j5.355 | 0.852 | 4.565 | Swing between some units of Ningxia and the whole grid Units #1, #2 of Zhongning, Ningxia = 0.0003 Units #1, #2 of Liujiaxia = 0.00016 | Units #1, #2 of Zhongning, Ningxia = 1 Units #1, #2 of Liujiaxia, Gansu = 0.65 Units #1, #3 of Aluminum Manufacturer, Gansu = 0.598 |
3 | −0.211 ±j6.566 | 1.045 | 3.208 | Swing between some units of Gansu and Ningxia and the whole grid Units #1, #2 of the thermal power plants in western Ningxia = 0.0003 Unit #4, Dam Power Plant, Ningxia = 0.00041 | Units #1, #3 of Aluminum Manufacturer, Gansu = 1 Unit #4, Dam Power Plant, Ningxia = 0.87 |
4 | −0.446 ±j6.568 | 1.045 | 6.777 | Swing between the units in the radiation range of Hexi and the whole grid Units #1, #4 of Xiliushui, Gansu = 0.0029, Unit #1 = 0.0028 | Unit #2 of Xiliushui, Gansu = 1, Units #3, #4 = 0.945 |
5 | −0.053 ±j6.990 | 1.112 | 0.761 | Swing among the unit groups of the Ningxia grid, the radiation network of Gansu Hexi, and the ring network of Hexi Units #1, #2 of Jingyuan Power Plant, Gansu = 0.00021 | Units #1, #3 of aluminum manufacturer, Gansu = 1; Units #1, #4 of Jingyuan Power Plant, Gansu = 0.761 |
6 | −0.068 ±j7.122 | 1.133 | 0.949 | Swing among the unit groups of the radiation network of Gansu Hexi and the Ningxia grid Units #1, #2 of Jingyuan, Gansu = 0.0021 | Units #1, #2 of Lanzhou Thermal Power Plant, Gansu = 1; Units #1, #2 of Jingyuan, Gansu = 0.48 |
7 | −0.425 ±j8.314 | 1.323 | 5.104 | Swing between the units of the radiation network of Hexi, Gansu, and the units of the Hexi ring network and Ningxia Unit #1 of 803 Power Plant, Gansu = 0.00096; Unit #2 of Xiliushui = 0.00099; Zhangye Power Plant = 0.00091 | Unit #1, 803 Power Plant = 1 Units #1, #2 of Zhangye Power Plant = 0.903 |
8 | −0.545 ±j9.574 | 1.524 | 5.684 | Swing among the units in the radiation network of Hexi, Gansu Unit #1, 803 Power Plant = 0.012; Units #1, #2 of Zhangye Power Plant = 0.0069 | Unit #1, 803 Power Plant = 1 Units #1, #2 of Zhangye Power Plant = 0.335 |
Table 4.5
Relevant Swing Mode Characteristics in Summer Minimum Mode, 2010, before the Wind Farms in Jiuquan Region Are Integrated (Not Provided with Serial Compensating Capacitors, Integrated with Xinjiang)
Mode | Characteristic Root | Damping Frequency (Hz) | Damping Ratio (%) | Modal Analysis | Participant Factor |
1 | −0.062 ±j3.948 | 0.706 | 1.563 | Swing between the units of Gansu and the radiation network of Hexi, Gansu, and the units of Ningxia Unit #1, technical improved, Ningxiashi = 0.00062 Units #1, #4 of Hadebute, Xinjiang = 0.00043 | Unit #1, technical improved, Ningxiashi = 1; Units #1, #2 of Luntai Thermal Power Plant, Xinjiang = 0.36 |
2 | −0.173 ±j4.370 | 0.852 | 3.966 | Swing between the units of Hexing Ring Network, Gansu, and Qinghai, and the units of Xinjiang Units #1, #2 of Liujiaxia = 0.00019 Unit #1, technical improved, Ningxiashi = 0.00016 | Units #1, #2 of Liujiaxia, Gansu = 1 Unit #1, technical improved, Ningxiashi = 0.454 |
3 | −0.216 ±j4.989 | 1.045 | 4.332 | Swing among some units of Ningxia, the units of Xinjiang, and the units of Qinghai Unit #1, technical improved, Ningxiashi = 0.00037 Units #1, #2 of Zhongning Power Plant = 0.00023 | Units #1, #2 of Liujiaxia, Gansu = 0.35 Unit #1, technical improved, Ningxiashi = 1 |
4 | −0.221 ±j5.250 | 1.045 | 4.203 | Swing between the units of Xinjiang and Ningxia and the units of Gansu and Qinghai Units #1, #2 of Zhongning Power Plant, Ningxia = 0.00033 Units #1, #2 of Liujiaxia = 0.00015 | Units #1, #2 of Zhongning Power Plant, Ningxia = 1 Units #1, #3 of Aluminum Manufacturer, Gansu = 0.548 |
5 | −0.389 ±j6.269 | 1.112 | 6.189 | Swing among the units in the radiation network of Hexi, Gansu, the units of the ring network of Hexi, and some units of Qinghai Units #3, #4 of Xiliushui, Gansu = 0.0036; Units #1, #2 = 0.0031 | Units #3, #4 of Xiliushui, Gansu = 1; Units #1, #2 = 0.75 |
6 | −0.022 ±j8.674 | 1.133 | 0.253 | Swing among the units in the radiation network of Hexi, Gansu, the units of the ring network of Hexi, and some units of Qinghai Units #1, #4 of Jingyuan, Gansu = 0.00029 | Units #1, #4 of Jingyuan, Gansu = 1 |
7 | −0.173 ±j9.088 | 1.323 | 1.902 | Swing between some units in Qinghai and the ring network of Hexi, Gansu Units #3, #10 of Hexi Salt Works, Gansu = 0.0014; Unit #1 of Tiecheng = 0.00097 | Units #3–10 of Hexi Salt Works, Gansu = 1 |
8 | −0.428 ±j9.174 | 1.524 | 4.659 | Swing among the units in the radiation network of Hexi Unit #1 of 803 Power Plant, Gansu = 0.0137; Unit #1 of Erlongshan = 0.0075; Unit #1 of Dagushan = 0.0073 | Unit #1 of 803 Power Plant, Gansu = 1 Units #1, #2 of Jiure #3 Power Plant = 0.41 |
Table 4.6
Damping Variation of Relevant Modes at Various Output Levels of WTGs
Mode | Damping Ratio at Various Modes (%) | |||
Zero Output of Wind Farms | 30% Limit Output | 60% Limit Output | 100% Limit Output | |
1 | 1.563 | 3.912 | 2.718 | 0.264 |
2 | 3.966 | 3.357 | 3.107 | 3.891 |
3 | 4.332 | 4.362 | 4.346 | 4.338 |
4 | 4.203 | 4.281 | 4.265 | 4.247 |
5 | 6.189 | 6.600 | 6.718 | 6.657 |
6 | 0.253 | 0.26 | 0.264 | 0.267 |
7 | 1.902 | 1.900 | 1.897 | 1.895 |
8 | 4.659 | 4.434 | 4.580 | 4.607 |
Table 4.7
Relevant Swing Mode Characteristics in Summer Minimum Mode, 2010, before the Wind Farms in Jiuquan Region Are Integrated (Provided with Serial Compensating Capacitors, and Integrated with Xinjiang)
Mode | Characteristic Root | Damping Frequency (Hz) | Damping Ratio (%) | Modal Analysis | Participant Factor |
1 | −0.051 ±j4.161 | 0.662 | 1.229 | Swing between the units of Gansu and the radiation network of Hexi, Gansu, and the units of Ningxia Unit #1, technical improved, Ningxiashi = 0.0017 Units #1, #4 of Hadebute, Xinjiang = 0.0009 | Unit #1, technical improved, Ningxiashi = 1 Units #1, #2 of Luntai Thermal Power Plant, Xinjiang = 0.52 |
2 | −0.174 ±j4.415 | 0.703 | 3.942 | Swing between the units of Hexing Ring Network, Gansu, and Qinghai, and the units of Xinjiang Units #1, #2 of Liujiaxia = 0.00023 Unit #1, technical improved, Ningxiashi = 0.0002 | Units #1, #2 of Liujiaxia, Gansu = 1 Unit #1, technical improved, Ningxiashi = 0.491 |
3 | −0.202 ±j4.996 | 0.795 | 4.048 | Swing among some units of Ningxia, the units of Xinjiang, and the units of Qinghai Unit #1, technical improved, Ningxiashi = 0.00037 Units #1, #2 of Zhongning Power Plant = 0.00023 | Units #1, #2 of Liujiaxia, Gansu = 0.58 Unit #1, technical improved, Ningxiashi = 1 |
4 | −0.213 ±j5.269 | 0.839 | 4.037 | Swing between the units of Xinjiang, Ningxia and the units of Gansu, Qinghai Units #1, #2 of Zhongning Power Plant = 0.00052 Units #1, #2 of Liujiaxia = 0.00035 | Units #1, #2 of Zhongning Power Plant, Ningxia = 1 Units #1, #3 of Aluminum Manufacturer, Gansu = 0.593 |
5 | −0.417 ±j6.331 | 1.008 | 6.571 | Swing among the units in the radiation network of Hexi, Gansu, the units of the ring network of Hexi, and some units of Qinghai Units #3, #4 of Xiliushui, Gansu = 0.0039; Units #1, #2 = 0.0027 | Units #3, #4 of Xiliushui, Gansu = 1; Units #1, #2 = 0.71 |
6 | −0.022 ±j8.705 | 1.385 | 0.252 | Swing among the units in the radiation network of Hexi, Gansu, the units of the ring network of Hexi, and some units of Qinghai Units #1, #4 of Jingyuan, Gansu = 0.00025 | Units #1, #4 of Jingyuan, Gansu = 1 |
7 | −0.175 ±j9.109 | 1.450 | 1.920 | Swing between the units of Qinghai and some units of the ring network of Hexi, Gansu Units #3, #10 of Hexi Salt Works = 0.0031 Unit #1 of Tiecheng = 0.0012 | Units #3, #10 of Hexi Salt Works, Gansu = 1 |
8 | −0.448 ±j9.236 | 1.470 | 4.850 | Swing among the units in the radiation network of Hexi Unit #1 of 803 Power Plant, Gansu = 0.0072; Unit #1 of Erlongshan = 0.0043 Unit #1 of Dagushan = 0.0042 | Unit #1 of 803 Power Plant, Gansu = 1 Units #1, #2 of Jiure #3 Power Plant = 0.556 |
Table 4.8
Damping Variation of Relevant Modes at Various Output Levels of WTGs
Mode | Damping Ratio at Various Modes (%) | |||
Zero Output of Wind Farms | 30% Limit Output | 60% Limit Output | 100% Limit Output | |
1 | 1.229 | 1.091 | 0.674 | 0.143 |
2 | 3.942 | 3.532 | 3.215 | 3.064 |
3 | 4.048 | 4.089 | 4.122 | 4.189 |
4 | 4.037 | 4.144 | 4.159 | 4.237 |
5 | 6.571 | 6.970 | 6.858 | 6.523 |
6 | 0.252 | 0.261 | 0.270 | 0.258 |
7 | 1.920 | 1.914 | 1.911 | 1.908 |
8 | 4.850 | 4.761 | 4.721 | 4.554 |
Table 4.9
Voltage Levels of Hexi Buses in Typical Mode (kV)
Bus | Hami S/S | Dunhuang S/S | Jiuquan S/S | Hexi S/S | Wusheng S/S |
750 kV bus | 750/330 kV bus | 750/330 kV bus | 750/330 kV bus | 750/330 kV bus | |
Voltage | 774.2 | 771.2/356.8 | 766.1/361.2 | 760.5/350.6 | 763.5/348.3 |
Bus | Qiaoxi wind power step-up S/S | Yumen S/S | Jiayuguan S/S | Zhangye S/S | Liangzhou S/S |
330 kV bus | 330 kV bus | 330 kV bus | 330 kV bus | 330 kV bus | |
Voltage | 357.1 | 361.4 | 360.4 | 356.2 | 348.5 |
Table 4.10
Frequency Stability after Large-Scale WTGs Are Disintegrated from the System
Scheme | Parameter | |||
Type of Fault | DC Modulation Scheme | Load Disintegrated by Low-Frequency Load-Shedding Protection Action | System Frequency Variation after Fault | |
I | WTGs of 3000 MW tripped without fault | 49.5 Hz: DC modulation starts; 49.3 Hz: 1 s delay; DC power rapidly reduced in Debao: 1200 MW | Low-frequency load-shedding protection act to disintegrate 2800 MW loads in the first round | Minimum frequency: 48.98 Hz; stable frequency: 49.95 Hz |
II | 49.5 Hz: DC modulation starts; 49.3 Hz: 1 s delay; DC power rapidly reduced in Debao: 1500 MW | Low-frequency load-shedding protection act to disintegrate 2800 MW loads in the first round | Minimum frequency: 48.99 Hz; stable frequency: 50 Hz | |
III | 49.5 Hz: DC modulation starts; 49.3 Hz: 1 s delay; DC power rapidly reduced in Debao: 1800 MW | Not act | Minimum frequency: 49.12 Hz; stable frequency: 49.17 Hz | |
IV | 49.5 Hz: DC modulation starts; 49.3 Hz: 1 s delay; DC power rapidly reduced in Debao: 1200 MW; DC power rapidly reduced in Ningdong: 1000 MW | Not act | Minimum frequency: 49.18 Hz; stable frequency: 49.4 Hz | |
V | 49.5 Hz: DC modulation starts; 49.3 Hz: 1 s delay; DC power rapidly reduced in Debao: 1500 MW; DC power rapidly reduced in Ningdong: 1000 MW | Not act | Minimum frequency: 49.19 Hz; stable frequency: 49.53 Hz |
Table 4.11
System Voltage When the Inductive Reactive Power Generated by the Dynamic Reactive Compensator of the Wind Farm is Put into Service and When the Controllable HV Reactor of Dunhuang S/S is Put into Service
Bus | Mode | ||||
Reference | 75 Mvar inductive reactive power by the dynamic reactive compensator is put into service | 75 Mvar inductive reactive power by the controllable HV reactor is put into service | |||
Voltage amplitude (kV) | Voltage amplitude (kV) | Voltage fluctuation (%) | Voltage amplitude (kV) | Voltage fluctuation (%) | |
750 kV side of Dunhuang S/S | 778.8 | 778.3 | −0.07 | 776.4 | −0.32 |
330 kV side of Dunhuang S/S | 351.6 | 351.3 | −0.09 | 350.9 | −0.21 |
750 kV side of Jiuquan S/S | 778.7 | 778.3 | −0.12 | 777.1 | −0.48 |
330 kV side of Jiuquan S/S | 351.5 | 351.4 | −0.03 | 351.1 | −0.12 |
330 kV side of Beidaqiao East S/S | 355.3 | 355 | −0.09 | 354.8 | −0.15 |
330 kV side of Beidaqiao West S/S | 352.6 | 352.3 | −0.09 | 352.00 | −0.18 |
330 kV side of Ganhekou West S/S | 355.3 | 354.9 | −0.12 | 354.8 | −0.15 |
330 kV side of Ganhekou East S/S | 355.1 | 354.6 | −0.15 | 354.5 | −0.18 |
330 kV side of Ganhekou North S/S | 354.5 | 354 | −0.15 | 353.9 | −0.18 |
330 kV side of Qiaowan S/S | 356.9 | 356.8 | −0.03 | 356.6 | −0.09 |
330 kV side of Yumen S/S | 355.9 | 355.8 | −0.03 | 355.6 | −0.09 |
330 kV side of Jiayuguan S/S | 351.1 | 351 | −0.03 | 350.70 | −0.12 |
330 kV side of Guazhou S/S | 347.7 | 347.4 | −0.09 | 347.10 | −0.18 |
Table 4.12
Enable/Disable of the LV Capacitor and LV Reactor of the 750 kV S/S and Arrangement of the Controllable HV Reactor Taps (Mvar)
Dunhuang S/S | Jiuquan S/S | ||||
LV capacitor | LV reactor | Controllable HV reactor | LV capacitor | LV reactor | Controllable HV reactor |
0 × 60 | 1 × 60 | 4 × 75 | 0 × 90 | 0 × 90 | 2 × 4 × 52.5 |
Hexi S/S | Wusheng S/S | ||||
LV capacitor | LV reactor | Controllable HV reactor | LV capacitor | LV reactor | |
0 × 90 | 0 × 90 | 2 × 4 × 52.5 | 0 × 120 | 0 × 120 |
Table 4.13
Voltage Setting of FACTS Control Nodes (kV)
Node | Beidaqiao East S/S | Beidaqiao West S/S | Ganhekou West S/S | Ganhekou East S/S | Ganhekou North S/S | Qiaowan S/S |
Voltage setting | 357 | 356 | 357 | 357 | 357 | 358 |
Node | Changma West S/S | Xiangyang S/S | Guazhou Huajing | Liuyuan S/S | Diwopu S/S | |
Voltage setting | 358 | 119 | 119 | 119 | 119 |
Table 4.14
Voltage Setting of FACTS Control Nodes (kV)
Node | Dunhuang S/S | Jiuquan S/S | Hexi S/S | Beidaqiao East S/S | Beidaqiao West S/S | Ganhekou West S/S | Ganhekou East S/S |
Voltage setting | 779 | 781 | 771 | 355 | 353 | 355 | 355 |
Node | Ganhekou North S/S | Qiaowan S/S | Changma West S/S | Xiangyang S/S | Guazhou Huajing S/S | Liuyuan S/S | Diwopu S/S |
Voltage setting | 354 | 357 | 357 | 119 | 119 | 118 | 119 |
Table 4.15
750 kV Enable/Disable of LV Capacitors/LV Reactors and Taps of Controllable HV Reactors in 750 kV S/S (Mvar)
Dunhuang S/S | Jiuquan S/S | ||||
LV capacitor | LV reactor | Controllable HV reactor | LV capacitor | LV reactor | Controllable HV reactor |
0 × 60 | 5 × 60 | 3 × 75 | 0 × 90 | 4 × 90 | 2 × 3 × 52.5 |
Hexi S/S | Wusheng S/S | ||||
LV capacitor | LV reactor | Controllable HV reactor | LV capacitor | LV reactor | |
0 × 90 | 0 × 90 | 2 × 3 × 52.5 | 0 × 120 | 0 × 120 |
Table 4.16
Node Voltage Fluctuation Resulting from Up/Down by One Tap of the Controllable HV Reactors, and 10% Capacity Variation of the Dynamic Reactive Power Compensators in Hexi Region
Node | Initial Mode (kV) | Controllable HV Reactor of Dunhuang S/S | Controllable HV Reactor of Jiuquan S/S | Controllable HV Reactor of Hexi S/S | Capacitive Capacity of Dynamic Reactive Power Compensators in Hexi Region | ||||
Down by One Tap | Up by One Tap | Down by One Tap | Up by One Tap | Down by One Tap | Up by One Tap | Up by 10% | Down by 10% | ||
750 kV side of Dunhuang S/S | 779.9 | 2.3 | −2.2 | 1.1 | −1.1 | 0.4 | −0.3 | 0.4 | −0.4 |
750 kV side of Jiuquan S/S | 781.3 | 1.4 | −1.3 | 1.9 | −1.8 | 0.6 | −0.5 | 0.3 | −0.3 |
750 kV side of Hexi S/S | 771.6 | 0.8 | −0.8 | 0.6 | −0.6 | 1.7 | −1.7 | 0.2 | −0.2 |
Beidaqiao East S/S | 355.7 | 0.5 | −0.5 | 0.3 | −0.2 | 0.1 | 0 | 0.3 | −0.2 |
Beidaqiao West S/S | 353.2 | 0.6 | −0.7 | 0.3 | −0.4 | 0 | −0.1 | 0.2 | −0.3 |
Ganhekou West S/S | 355.7 | 0.5 | −0.5 | 0.3 | −0.2 | 0.1 | 0 | 0.3 | −0.3 |
Ganhekou East S/S | 355.4 | 0.5 | −0.5 | 0.3 | −0.2 | 0.1 | −0.1 | 0.3 | −0.3 |
Ganhekou North S/S | 354.9 | 0.5 | −0.6 | 0.3 | −0.3 | 0.1 | −0.1 | 0.3 | −0.3 |
Qiaowan S/S | 357.3 | 0.3 | −0.4 | 0.2 | −0.3 | 0 | −0.1 | 0.3 | −0.4 |
Changma West S/S | 357.3 | 0.2 | −0.2 | 0.2 | −0.1 | 0.1 | 0 | 0.4 | −0.3 |
Diwopu S/S | 119.8 | 0 | −0.1 | 0 | −0.1 | 0 | 0 | 0.2 | −0.2 |
Xiangyang S/S | 119.3 | 0.1 | −0.1 | 0.1 | 0 | 0 | 0 | 0.1 | −0.1 |
Guazhou Huajing S/S | 119.4 | 0.1 | −0.1 | 0 | −0.1 | 0 | 0 | 0.1 | −0.2 |
Liuyuan S/S | 118.7 | 0.1 | −0.1 | 0.1 | −0.1 | 0 | 0 | 0.1 | −0.1 |
Table 4.17
Voltage Fluctuation and Reactive Power Compensator Actions in the Robust Strategy and the Summer Maximum Load Mode, 2010, in Case of Wind Power Output Variation
Wind Power (MW) | 0 | 500 | 1000 | 1500 | 2000 | 2500 | 3188 | |
750 kV side of Dunhuang S/S (kV) | 787 | 785.4 | 782.2 | 777.4 | 771.2 | 764.5 | 760.7 | |
750 kV side of Jiuquan S/S (kV) | 790 | 787.4 | 782.9 | 776.5 | 768.3 | 760 | 759.6 | |
750 kV side of Hexi S/S (kV) | 777.7 | 775.1 | 770.6 | 763.9 | 756.7 | 753.6 | 750.2 | |
750 kV side of Wusheng S/S (kV) | 772.3 | 771 | 767.9 | 763.2 | 757.5 | 753.5 | 750.7 | |
Beidaqiao East S/S (kV) | 358.6 | 358.3 | 357.6 | 356.3 | 354.6 | 352.6 | 350.8 | |
Beidaqiao West S/S (kV) | 357.1 | 356.6 | 355.5 | 353.8 | 351.5 | 349 | 346.8 | |
Ganhekou West S/S (kV) | 358.6 | 358.3 | 357.6 | 356.3 | 354.5 | 352.5 | 350.8 | |
Ganhekou East S/S (kV) | 358.4 | 358.1 | 357.3 | 356 | 354.2 | 352.1 | 350.3 | |
Ganhekou North S/S (kV) | 358.2 | 357.8 | 356.9 | 355.5 | 353.6 | 351.4 | 349.5 | |
Qiaowan S/S (kV) | 359.7 | 359.6 | 359.1 | 358.1 | 356.7 | 355 | 353.6 | |
Changma West S/S (kV) | 359.5 | 359.5 | 359.2 | 358.4 | 357.2 | 355.8 | 354.6 | |
Diwopu S/S (kV) | 120.5 | 120.5 | 120.3 | 119.8 | 119.2 | 118.4 | 117.2 | |
Xiangyang S/S (kV) | 119.7 | 119.8 | 119.7 | 119.3 | 118.8 | 118.2 | 117.2 | |
Guazhou Huajing S/S (kV) | 119.8 | 119.8 | 119.7 | 119.4 | 118.9 | 118.2 | 117.3 | |
Liuyuan S/S (kV) | 119.5 | 119.4 | 119.1 | 118.6 | 117.9 | 117 | 115.8 | |
Table Continued |
Wind Power (MW) | 0 | 500 | 1000 | 1500 | 2000 | 2500 | 3188 | |
Dunhuang S/S | Tap position of controllable HV reactor | 4 | 4 | 4 | 4 | 4 | 4 | 4 |
Sets of LV capacitors | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
Sets of LV reactors | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Jiuquan S/S | Tap position of controllable HV reactor | (4,4) | (4,4) | (4,4) | (4,4) | (4,4) | (4,4) | (1,1) |
Sets of LV capacitors | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
Sets of LV reactors | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
Hexi S/S | Tap position of controllable HV reactor | (4,4) | (4,4) | (4,4) | (4,4) | (4,3) | (1,1) | (1,1) |
Sets of LV capacitors | 0 | 0 | 0 | 0 | 0 | 0 | 3 | |
Sets of LV reactors | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
Wusheng S/S | Sets of LV capacitors | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Sets of LV reactors | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Table 4.18
Voltage Fluctuation and Reactive Power Compensator Actions in the Fine Strategy and the Summer Maximum Mode, 2010, in Case of Wind Power Output Variation
Wind Power (MW) | 0 | 500 | 1000 | 1500 | 2000 | 2500 | 3188 | |
750 kV side of Dunhuang S/S (kV) | 782.3 | 783.1 | 779.9 | 776.7 | 775.3 | 771.8 | 761.4 | |
750 kV side of Jiuquan S/S (kV) | 784.2 | 785.8 | 781.3 | 777.4 | 777.3 | 769.8 | 758.2 | |
750 kV side of Hexi S/S (kV) | 775.8 | 776 | 771.6 | 766.6 | 767.5 | 759 | 752.1 | |
750 kV side of Wusheng S/S (kV) | 771.2 | 771.4 | 768.8 | 765.5 | 765 | 758.8 | 753.1 | |
Beidaqiao East S/S (kV) | 356.2 | 356.5 | 355.7 | 354.8 | 354.2 | 352.9 | 349.6 | |
Beidaqiao West S/S (kV) | 354.1 | 354.3 | 353.2 | 351.9 | 351.1 | 349.5 | 345.4 | |
Ganhekou West S/S (kV) | 356.2 | 356.5 | 355.7 | 354.8 | 354.2 | 352.9 | 349.6 | |
Ganhekou East S/S (kV) | 356 | 356.2 | 355.4 | 354.5 | 353.8 | 352.5 | 349.2 | |
Ganhekou North S/S (kV) | 355.6 | 355.8 | 354.9 | 353.9 | 353.2 | 351.8 | 348.2 | |
Qiaowan S/S (kV) | 357.4 | 357.8 | 357.3 | 356.6 | 356.1 | 355 | 352.2 | |
Changma West S/S (kV) | 357.2 | 357.7 | 357.3 | 356.8 | 356.5 | 355.3 | 352.9 | |
Table Continued |
Wind Power (MW) | 0 | 500 | 1000 | 1500 | 2000 | 2500 | 3188 | |
Diwopu S/S (kV) | 119.9 | 120 | 119.8 | 119.4 | 119 | 118.2 | 116.8 | |
Xiangyang S/S (kV) | 119.2 | 119.4 | 119.3 | 119.1 | 118.8 | 118.2 | 117 | |
Guangzhou Huajing S/S (kV) | 119.3 | 119.5 | 119.4 | 119.1 | 118.8 | 118.3 | 117.1 | |
Liuyuan S/S (kV) | 118.9 | 119 | 118.7 | 118.3 | 117.8 | 117.1 | 115.5 | |
Dunhuang S/S | Tap position of controllable HV reactor | 3 | 3 | 3 | 3 | 3 | 1 | 1 |
Sets of LV capacitors | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
Sets of LV reactors | 5 | 5 | 5 | 5 | 5 | 5 | 5 | |
Jiuquan S/S | Tap position of controllable HV reactor | (4,4) | (3,3) | (3,3) | (3,2) | (1,1) | (1,1) | (1,1) |
Sets of LV capacitors | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
Sets of LV reactors | 4 | 4 | 4 | 4 | 4 | 4 | 4 | |
Hexi S/S | Tap position of controllable HV reactor | (4,3) | (3,3) | (3,3) | (3,3) | (1,1) | (1,1) | (1,1) |
Sets of LV capacitors | 0 | 0 | 0 | 0 | 0 | 0 | 4 | |
Sets of LV reactors | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
Wusheng S/S | Sets of LV capacitors | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Sets of LV reactors | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Table 4.19
Impact of SVC Action Delay Variation on System Stability
Operating Mode | SVC Action Delay (s) | Limitation Fault | Stability |
Summer maximum mode, not provided with series compensation capacitors and controllable HV reactors | 0.1 (calculated initial value) | “Three-permanent” fault on Jiuquan side of the Jiuquan-Hexi 750 kV transmission line | Stable |
0.11 (critical stable value) | Stable | ||
0.12 (critical out-of-stability value) | The thermal power units in Jiuquan Region and Xinjiang lose stability of the power angle with respect to the Northwest Main Grid. |
Table 4.20
Impact of SVC Action Delay Variation on System Stability
Operating Mode | SVC Action Delay (s) | Limitation Fault | Stability |
Summer maximum mode, not provided with series compensation capacitors and controllable HV reactors | 0.1 (calculated initial value) | “Three-permanent” fault on Jiuquan side of the Jiuquan-Hexi 750 kV transmission line | Stable |
0.11 (critical stable value) | Stable | ||
0.12 (critical out-of-stability value) | The voltage of Dunhuang and Jiuquan Substations are excessively low, and the thermal power units in Jiuquan Region and Xinjiang lose stability of the power angle with respect to the Northwest Main Grid. |
Table 4.21
Impact of SVC Gain Variation on System Stability
Operating Mode | SVC Gain | Limitation Fault | Stability |
Summer maximum mode, not provided with series compensation capacitors and controllable HV reactors | 200 | “Three-permanent” fault on Jiuquan side of the Jiuquan-Hexi 750 kV transmission line | Stable |
50 (calculated initial value) | Stable | ||
23 (critical stable value) | Stable | ||
22 (critical out-of-stability value) | The thermal power units in Jiuquan Region and Xinjiang lose stability of the power angle with respect to the Northwest Main Grid. |
Table 4.22
Impact of SVC Gain Variation on System Stability
Operating Mode | SVC Gain | Limitation Fault | Stability |
Summer maximum load mode, not provided with series compensation capacitors and controllable HV reactors | 200 | “Three-permanent” fault on Jiuquan side of the Jiuquan-Hexi 750 kV transmission line | Stable |
50 (calculated initial value) | Stable | ||
44 (critical stable value) | Stable | ||
43 (critical out-of-stability value) | The voltage of Dunhuang and Jiuquan Substations are excessively low, and the thermal power units in Jiuquan Region and Xinjiang lose stability of the power angle with respect to the Northwest Main Grid. |