This chapter introduces the technical specifications on integrated wind turbine generators and the method for modeling wind turbine generators, carries out the transient analysis of wind power generation, and analyzes the reactive power and voltage characteristics of wind farms. Finally, software for evaluating the transmission capability of wind power is introduced.
(3.1)
(3.2)
(3.3)
(3.4)
(3.5)
(3.6)
(3.7)
(3.8)
(3.9)
(3.10)
(3.11)
(3.12)
(3.13)
(3.14)
Table 3.1
αi,j Values for the DFIG Model
i | j | αi,j | i | j | αi,j | i | j | αi,j | i | j | αi,j | i | j | αi,j |
0 | 0 | −4.1909 × 10−1 | 1 | 0 | −6.7606 × 10−2 | 2 | 0 | 1.5727 × 10−2 | 3 | 0 | −8.6018 × 10−4 | 4 | 0 | 1.4787 × 10−5 |
1 | 2.1808 × 10−1 | 1 | 6.0405 × 10−2 | 1 | −1.0996 × 10−2 | 1 | 5.7051 × 10−4 | 1 | −9.4839 × 10−6 | |||||
2 | −1.2406 × 10−2 | 2 | −1.3934 × 10−2 | 2 | 2.1495 × 10−3 | 2 | −1.0479 × 10−4 | 2 | 1.6167 × 10−6 | |||||
3 | −1.3365 × 10−4 | 3 | 1.0683 × 10−3 | 3 | −1.4855 × 10−4 | 3 | 5.9924 × 10−6 | 3 | −7.1535 × 10−8 | |||||
4 | 1.1524 × 10−5 | 4 | −2.3895 × 10−5 | 4 | 2.7937 × 10−6 | 4 | −8.9194 × 10−8 | 4 | 4.9686 × 10−10 |
(3.15)
Table 3.3
Pitch Angle Control Parameters of DFIG Model
Name of Variable | Recommended Parameter | Name of Variable | Recommended Parameter |
Kpp | 150 | Pmin(p.u.) | 0.1 |
Kip | 25 | dP/dtmax(p.u./s) | 0.45 |
Tp(s) | 0.30 | dP/dtmax(p.u./s) | −0.45 |
θmax(°) | 27 | kpc | 3.0 |
θmin(°) | 0.0 | Kic | 30.0 |
d/dtmax(°/s) | 10.0 | kptrq | 3.0 |
d/dtmin(°/s) | −10.0 | kitrq | 0.6 |
Pmax(p.u.) | 1.12 | Tpc | 0.05 |
(3.16)
(3.17)
(3.18)
Table 3.5
Transient Stable Limits of Detailed and Multiple Wind Farm Models in Constant Control Mode
Various Wind Farm Models | Hydropower Output: Fixed at 350 MW; Thermal Power as the Balance Node; Wind Power Output: Continuously Rise |
Limit output of WTGs in the detailed wind farm model (MW) | 651 |
Limit output of WTGs in the multiple wind farm equivalent model (MW) | 620 |
Table 3.6
Transient Stable Limits of Detailed and Multiple Wind Farm Models in the Constant Power Factor Control Mode
Various Wind Farm Models | Hydropower Output: Fixed at 350 MW; Thermal Power as the Balance Node; Wind Power Output: Continuously Rise |
Limit output of WTGs in the detailed wind farm model (MW) | 478 |
Limit output of WTGs in the multiple wind farm equivalent model (MW) | 462 |
Table 3.7
Simulation Results of WTGs Disintegrated from the Grid and Shut Down due to Insufficient LVRT Capability
No. | Simulation Results |
1 | 7.0 cycle, generator “1Z101 0.7” undervoltage and overvoltage relay RE act (acting voltage: 0.8500 p.u.). 7.0 cycle, disintegrate WTG “1Z101 0.7” power 0.12 MW (1 set) |
2 | 7.0 cycle, generator “1Z102 0.7” undervoltage and overvoltage relay RE act (acting voltage: 0.8500 p.u.). 7.0 cycle, disintegrate WTG “1Z102 0.7” power 0.12 MW (1 set) |
3 | 7.0 cycle, generator “1Z103 0.7” undervoltage and overvoltage relay RE act (acting voltage: 0.8500 p.u.). 7.0 cycle, disintegrate WTG “1Z103 0.7” power 0.12 MW (1 set) |
4 | 7.0 cycle, generator “1Z104 0.7” undervoltage and overvoltage relay RE act (acting voltage: 0.8500 p.u.). 7.0 cycle, disintegrate WTG “1Z104 0.7” power 0.12 MW (1 set) |
…… | …… |
Total output of WTGs disintegrated (MW) | 27.72 |
Table 3.8
Calculation Results of Grid Stability in Case of WTGs Integrated to the Grid at 330 kV in Constant Voltage Mode, Xinjiang Integrated with Northwest Grid, Provided with Serial Compensating Capacitors/Controllable HV Reactors, 2010
Operating Mode | Limit Output of WTGs (MW) | Power of Jiuquan-Hexi Line (MW) | Out-of-Stability Mode | Remarks |
Summer maximum | 3400 | 4912 | The Jiuquan-Hexi line has “three permanent” N-1 fault on Jiuquan side, the voltage of Dunhuang, Jiuquan Substations is excessively low, and the power angle of the thermal units in Jiuquan loses stability in terms of the Northwest Main Grid | Some FSIGs, DFIGs that are not designed with LVRT capability and integrated to Guazhou, Yumen Substations at 110 kV are shut down |
Summer minimum | 3520 | 4972 | ||
Winter minimum | 3492 | 5010 | ||
Winter maximum | 3444 | 4911 |
Table 3.9
Calculation Results of Grid Stability in Case of WTGs Integrated to the Grid at 330 kV in Constant Power Factor Mode, Xinjiang Integrated with the Northwest Grid, Provided with Serial Compensating Capacitors/Controllable HV Reactors, 2010
Operating Mode | Limit Output of WTGs (MW) | Power of Jiuquan-Hexi Line (MW) | Out-of-Stability Mode | Remarks |
Summer maximum | 2142 | 3710 | The Jiuquan-Hexi line has “three permanent” N-1 fault on Jiuquan side, the voltage of Dunhuang, Jiuquan Substations is excessively low, and subsequently the power angle of the thermal units in Jiuquan loses stability in terms of the Northwest Main Grid | Some FSIGs that are not designed with LVRT capability and integrated to Guazhou, Yumen substations at 110 kV are shut down |
Summer minimum | 2142 | 3629 | Some FSIGs, DFIGs that are not designed with LVRT capability and integrated to Guazhou, Yumen Substations at 110 kV are shut down; and some DFIGs, D-PMSGs that are designed with LVRT capability and integrated to Dunhuang Substation at 330 kV are shut down (less than 0.9 p.u. 150 cycles). | |
Winter maximum | 2084 | 3604 | ||
Winter minimum | 2170 | 3740 | Some FSIGs, DFIGs that are not designed with LVRT capability and integrated to Guazhou, Yumen Substations at 110 kV are shut down (the constant power factor can offer weak support to voltage). |
Table 3.10
Calculation Results of Grid Stability in Case of WTGs Integrated to the Grid at 330 kV in Constant Voltage Mode, Xinjiang Integrated with Northwest Grid, Not Provided with Serial Compensating Capacitors/Controllable HV Reactors, 2010
Operating Mode | Limit Output of WTGs (MW) | Power of Jiuquan-Hexi Line (MW) | Out-of-Stability Mode | Remarks |
Summer maximum | 1736 | 3287 | The Jiuquan-Hexi line has “three permanent” N-1 fault on Jiuquan side, the power angle of the thermal units in Jiuquan Region and Xinjiang loses stability in terms of the Northwest Main Grid | Some FSIGs, DFIGs that are not designed with LVRT capability and integrated to Guazhou, Yumen Substations at 110 kV are shut down |
Summer minimum | 1820 | 3312 | ||
Winter maximum | 1778 | 3356 | ||
Winter minimum | 1794 | 3320 |
Table 3.11
Calculation Results of Grid Stability in Case of WTGs Integrated to the Grid at 330 kV in Constant Power Factor Mode, Xinjiang Integrated with Northwest Grid, Not Provided with Serial Compensating Capacitors/Controllable HV Reactors, 2010
Operating Mode | Limit Output of WTGs (MW) | Power of Jiuquan-Hexi Line (MW) | Out-of-Stability Mode | Remarks |
Summer maximum | 1210 | 2802 | The Jiuquan-Hexi line has “three permanent” N-1 fault on Jiuquan side, the voltage of Dunhuang and Jiuquan is excessively low, and the power angle of the thermal units in Jiuquan Region and Xinjiang loses stability in terms of the Northwest Main Grid | Most of the FSIGs, DFIGs that are not designed with LVRT capability and integrated to Guazhou, Yumen Substations at 110 kV are shut down. |
Summer minimum | 1289 | 2832 | ||
Winter maximum | 1217 | 2756 | ||
Winter minimum | 1243 | 2838 |
Table 3.12
Calculation Results of Grid Stability in Summer Maximum, 2010, in Case of WTGs Integrated to the Grid at 330 kV in Constant Voltage Mode, Xinjiang Not Integrated with Northwest Grid, Not Provided with Serial Compensating Capacitors/Controllable HV Reactors
Integration Mode | Limit Output of WTGs (MW) | Power of Jiuquan-Hexi Line (MW) | Out-of-Stability Mode | Remarks |
Xinjiang not integrated to the Northwest Grid | 1693 | 2264 | The Jiuquan-Hexi line has “three permanent” N-1 fault on Jiuquan side, the power angle of the thermal units in Jiuquan Region loses stability in terms of the Northwest Main Grid | Some FSIGs, DFIGs that are not designed with LVRT capability and integrated to Guazhou, Yumen Substations at 110 kV are shut down |
Hami integrated to the Northwest Grid | 760 | 2331 |
Table 3.13
Calculation Results of Grid Stability in Summer Maximum, 2010, in Case of WTGs Integrated to the Grid at 330 kV in Constant Power Factor Mode, Xinjiang Not Integrated with Northwest Grid, Not Provided with Serial Compensating Capacitors/Controllable HV Reactors
Integration Mode | Limit Output of WTGs (MW) | Power of Jiuquan-Hexi Line (MW) | Out-of-Stability Mode | Remarks |
Xinjiang not integrated to the Northwest Grid | 580 | 1192 | The Jiuquan-Hexi line has “three permanent” N-1 fault on Jiuquan side, the voltage of Dunhuang and Jiuquan is excessively low, and the power angle of the thermal units in Jiuquan Region loses stability in terms of the Northwest Main Grid | Most of the FSIGs, DFIGs that are not designed with LVRT capability and integrated to Guazhou, Yumen Substations at 110 kV are shut down; and some D-PMSGs integrated at 110 kV are shut down. Some DFIGs that are designed with LVRT capability and integrated at 330 kV are shut down |
Hami integrated to the Northwest grid | 260 | 1816 |
Table 3.14
Total Output Comparisons of WTGs Disintegrated from the Grid Before/After LVRT Capability Change on WTGs
Originally Provided with LVRT Capability | Changed as Not Provided with LVRT Capability |
Some FSIGs, DFIGs (156.4 MW) that are integrated to Guazhou, Yumen Substations at 110 kV and not provided with LVRT capability are disintegrated from the grid | Some FSIGs, DFIGs (132.1 MW) that are integrated to Guazhou, Yumen Substations at 110 kV and not provided with LVRT capability are disintegrated from the grid; and some DFIGs (729 MW) that are integrated to Dunhuang Substation at 330 kV and changed as not provided with LVRT capability are disintegrated from the grid; the total output of the above two is 861.1 MW |
Table 3.15
Simulation Results of WTGs Disintegrated Concerning LVRT, at WTG Limit Output in Summer Maximum, 2010, in Constant Power Factor Control Mode, After LVRT Capability is Changed
No. | Simulation Results |
1 | 7.0 cycle, generator “1Z101 0.7” undervoltage and overvoltage relay RE act (acting voltage: 0.8500 p.u.). 7.0 cycle, disintegrate WTG “1Z101 0.7” power 0.12 MW (1 set) |
2 | 7.0 cycle, generator “1Z102 0.7” undervoltage and overvoltage relay RE act (acting voltage: 0.8500 p.u.). 7.0 cycle, disintegrate WTG “1Z102 0.7” power 0.12 MW (1 set) |
…… | …… |
Cut off the output of FSIGs, DFIGs not provided with LVRT capability and disintegrated from the grid (MW) | 156.42 |
1 | 7.0 cycle, generator “7GX∗01 0.7” undervoltage and overvoltage relay RE act (acting voltage: 0.8500 p.u.). 7.0 cycle, disintegrate WTG “7GX∗01 0.7” power 1.35 MW (1 set) |
2 | 7.0 cycle, generator “7GX∗02 0.7” undervoltage and overvoltage relay RE act (acting voltage: 0.8500 p.u.). 7.0 cycle, disintegrate WTG “7GX∗02 0.7” power 1.35 MW (1 set) |
…… | …… |
Cut off the output of DFIGs changed to not provided with LVRT capability and disintegrated (MW) | 1131.3 |
1 | 150 cycle, generator “5BX001 0.7” undervoltage and overvoltage relay RE act (acting voltage: 0.9000 p.u.). 150.0 cycle, disintegrate WTG “5BX001 0.7” power 1.35 MW (1 set) |
2 | 150 cycle, generator “5BX002 0.7” undervoltage and overvoltage relay RE act (acting voltage: 0.9000 p.u.). 150.0 cycle, disintegrate WTG “5BX002 0.7” power 1.35 MW (1 set) |
…… | …… |
Cut off the output of DFIGs provided with LVRT capability disintegrated (MW) | 180.9 |
Cut off the output of total of the WTGs disintegrated (MW) | 1468.62 |
Table 3.16
Effect of WTG LVRT Capability on Limit Transmission Capacity of WTGs
Control Mode | Limit Output of WTGs (MW) | Power of Jiuquan-Hexi Line (MW) | Out-of-Stability Mode | Remarks |
Constant power factor control | 3000 | 4533 | The Jiuquan-Hexi line has “three permanent” N-1 fault on Jiuquan side, the voltage of Dunhuang and Jiuquan Substations is excessively low, and the power angle of the thermal units in Jiuquan Region loses stability in terms of the Northwest Main Grid, and the Xinjiang Grid is out of step in terms of the Northwest Main Grid | Most FSIGs, DFIGs that are integrated to Guazhou, Yumen Substations at 110 kV and not provided with LVRT capability are shut down; and most DFIGs that are integrated to Dunhuang Substation at 330 kV and not provided with LVRT capability are shut down (less than 0.85 p.u. for 7 cycles); and some DFIGs that are integrated to Dunhuang Substation at 330 kV and provided with LVRT capability are shut down (less than 0.9 p.u. for 150 cycles) |
Constant voltage control | 3400 | 4912 | Some FSIGs, DFIGs that are not designed with LVRT capability and integrated to Guazhou, Yumen Substations at 110 kV are shut down |
Table 3.17
Voltage at PCC, Active/Reactive Output of the Integrated Line in Case of Output Variation of Wind Farms
Electrical Quantity | Treatment of Electrical Wiring | |||||||||||
Integration of Wind Farm with Consideration to the Electrical Wiring | Integration of Wind Farm Ignoring Electrical Wiring | |||||||||||
Output of wind farm (MW) | 0 | 150 | 300 | 450 | 600 | 700 | 0 | 150 | 300 | 450 | 600 | 700 |
Voltage at PCC of wind farm (p.u.) | 0.9671 | 0.9695 | 0.9669 | 0.9589 | 0.9442 | 0.9291 | 0.9656 | 0.9682 | 0.9661 | 0.9589 | 0.9455 | 0.9318 |
Reactive power of the integrated line (Mvar) | 5.8 | −1 | −21.7 | −57.9 | −112.8 | −163.6 | 0 | −6.2 | −25.1 | −58.1 | −107.8 | −153.5 |
Active power of the integrated line (MW) | 0 | 149.8 | 298.9 | 447.4 | 595.5 | 695.6 | 0 | 150 | 300 | 450 | 600 | 700 |
Table 3.18
Comparisons of Reactive Voltage Control Output Results
Output of Wind Farm (MW) | 0 | 150 | 300 | 450 | 600 | 700 |
SVC-controlled quantities considering the internal electrical wiring of the wind farm (Mvar) | 11.6 | 2.1 | 12.0 | 41.8 | 92.0 | 137.5 |
SVC-controlled quantities ignoring the internal electrical wiring of the wind farm (Mvar) | 17.5 | 7.3 | 15.4 | 42.3 | 88.3 | 130.4 |
(3.19)
Table 3.19
Brief Introduction and Fast Index of Functions of the Evaluation Software
Category | Function Menu | Tool Button | Shortcut Key | Description |
Evaluation (P) | Evaluation of current mode (B) | F5 | Evaluate the currently selected mode in the evaluation configuration list of wind power modes | |
Evaluate all the modes (M) | Ctrl + F5 | Evaluate the files of the mode checked qualified in the evaluation configuration list of wind power modes | ||
End the calculation (E) | Shift + F5 | After the calculation for wind power evaluation starts, it may cause no result available or incomplete result if the limit calculation is stopped during calculation | ||
Statistics of WTG output (W) | F3 | Extract the options in the report of evaluation results for WTGs and carry out statistics and analysis on WTG output | ||
Export the result to Excel (X) | To output the evaluation result to Excel, the Excel software shall be preinstalled in the system | |||
Realize the function by sub-toolbar | ||||
Setting operation | Select the file associated with the column | According to the edit items in the table, select the associated data file | ||
Select several files | Several files can be selected at one time and they can be filled into the selected table by the suffix of the file; when the default suffix is used, all the configuration files can be selected at one time | |||
Definition of section | It is an indispensable configuration item for wind power evaluation to set the formation of sections and unit adjustment in the current mode | |||
Table Continued |
Category | Function Menu | Tool Button | Shortcut Key | Description |
Create a new blank mode record | To create a new blank mode record, the software will automatically show the serial number and the mode time number, where the time number can be manually modified and the serial number system will be automatically executed | |||
Create a mode record by paste | If there is the associated information on the mode clipboard, a new mode record can be created by direct use of the information on the clipboard | |||
Cut a mode record | Copy the currently selected mode record to the mode clipboard and delete the current record | |||
Copy a mode record | Copy the currently selected mode record to the mode clipboard | |||
Paste a mode record | Copy the record in the mode clipboard (if any) to the currently selected mode record | |||
Delete the selected record | Delete the currently selected mode record | |||
Delete all the mode records | Delete the mode records in all tables | |||
Open the configuration list | Open the configuration list previously saved | |||
Save the configuration list | Save the content of the current configuration list to the file | |||
View (V) | Main toolbar | Display and hide the main toolbar | ||
Status bar (S) | Display and hide the status bar | |||
Wind power evaluation guide (W) | Alt + W | Display the closed wind power evaluation guide window | ||
Help (H) | About the software (A) | Display the development information of the software |
Table 3.20
Information of Adjustable WTGs at TE (MW)
Adjusting and Control Sequence | Name of WTG | Maximum Active Output | Adjustable Lower Limit of Active Output | Adjustable Upper Limit of Active Output |
1 | Ganganhe G7 | 200 | 0 | 200 |
2 | Ganganhe G6 | 200 | 0 | 200 |
3 | Ganganhe G5 | 200 | 0 | 200 |
4 | Ganganhe G4 | 200 | 0 | 200 |
5 | Ganganhe G2 | 200 | 0 | 200 |
6 | Ganganhe G3 | 200 | 0 | 200 |
7 | Ganganhe G1 | 200 | 0 | 200 |
8 | Ganganhe G8 | 200 | 0 | 200 |
9 | Ganbeida G5 | 200 | 0 | 200 |
Table 3.21
Information of Adjustable WTGs at RE (MW)
Adjusting and Control Sequence | Name of WTG | Maximum Active Output | Adjustable Lower Limit of Active Output | Adjustable Upper Limit of Active Output |
1 | Ganjingyuan G6 | 300 | 0 | 300 |
2 | Ganjingyuan G5 | 300 | 200 | 300 |
3 | Ganjingyuan G4 | 200 | 0 | 200 |
4 | Ganjingyuan G3 | 200 | 0 | 200 |
5 | Ganjingyuan G2 | 200 | 0 | 200 |
6 | Ganjingyuan G1 | 200 | 0 | 200 |
7 | Ganjingyuan G7 | 300 | 0 | 300 |
8 | Ganjingyuan G8 | 300 | 0 | 300 |
Table 3.22
Comparisons of Manual and Software Automatic Calculation Results
Means of Calculation | No. of Section | Name of Section | Present Power Flow (MW) | Capacity of Section (MW) | Reason of Limit |
Software automatic calculation | 1 | “Jiuquan-Hexi 750 kV, Jiuquan-Zhangye 330 kV” | 2566.98 | 3734.92 | Transient stability limit |
Manual calculation | 1 | “Jiuquan-Hexi 750 kV, Jiuquan-Zhangye 330 kV” | 2569.9 | 3759.1 | After transient persistent, increasing oscillation, the oscillation will slowly attenuate |