10

Three-phase AC supply

Abdul R. Beig    Department of Electrical Engineering, The Petroleum Institute, Abu Dhabi, UAE

Abstract

This chapter presents the basic concepts and analysis of the balanced three-phase circuit. A brief review of generation of balanced three-phase voltages is presented. The three-phase connection of wye- and delta-connected sources, and wye- and delta-connected loads is given. The analysis of different types of three-phase networks is presented. The calculation of active, reactive, and apparent power in a balanced three-phase circuit is presented.

Keywords

three-phase circuits
balanced three-phase source
balanced three-phase load
balanced three-phase system
wye-connected source
delta-connected source
wye-connected load
delta-connected source
active power
reactive power
apparent power

10.1. Introduction

The three-phase system is an economical way of bulk power transmission over long distances and for distribution. The three-phase system consists of a three-phase voltage source connected to a three-phase load by means of transformers and transmission lines. Two types of connections are possible, namely delta (∆) connection and star or wye (Y) connection. The load and the source can be either in delta or star. The transmission line will be in delta connection. Normally the power system is operated in balanced three-phase condition. Most of the bulk loads such as industrial loads are three-phase balanced loads in nature. However, when there is a mix of single-phase and three-phase loads such as residential loads, the load will be unbalanced. Nevertheless, an unbalanced load can be resolved into a set of more than one balanced system. Hence, the analysis of a balanced system at steady state will be enough to understand three-phase systems.

10.2. Generation of three-phase voltages

The bulk of electricity is generated using three-phase alternating current (AC) generators also known as alternators. The AC generators are driven by hydroturbines, gas turbines, steam turbines, or internal combustion engines. AC generators have three separate windings distributed around the inner periphery of the stator [1]. The three windings corresponding to three phases of the system are electrically separated by 120°. The rotor consists of field windings or electromagnets and is rotated at synchronous speed by the prime mover. The rotatory magnetic field cuts the windings in the stator and according to Faraday’s law [1,2] voltages are induced in these windings.
The three-phase windings are designed such that the induced three-phase voltages are sinusoidal, have same frequency, same peak voltage, and are phase displaced by 120°. The three-phase voltages under balanced conditions are defined as in (10.1) and the waveforms are shown in Figure 10.1.

va=Vmsinωtvb=Vmsinωt2π3vc=Vmsinωt4π3orvc=Vmsinωt+2π3

image(10.1)
image
Figure 10.1 Waveforms of induced voltage in three-phase windings.
Let us denote these three phases as a, b, and c. Phase a voltage is taken as reference, then phase b voltage lags phase “a” by 120° (or 2π/3 rad) and phase “c” voltage lags phase “a” voltage by 240° (or 4π/3 rad). The phase sequence is a–b–c. Instead of a–b–c notation, the phases can also be donated by R (red)–Y (yellow)–B (blue) color code. The earlier mentioned phase sequence is referred to as positive phase sequence. If any of the phases are interchanged (e.g., phase “b” and phase “c” are interchanged) that is phase “c” lags phase “a” by 120° and phase “b” lags phase “a” by 240° then the resulting a-c-b phase sequence is referred as negative phase sequence.
For the past the few decades, major emphasis has been given on renewable energy sources such as wind energy, photovoltaic systems, fuel cells, etc. The generation of electricity from those sources is explained in Chapters 3, 4, and 6, respectively. In these types of electric sources three-phase electricity is generated with the help of direct current (DC) to AC converters [3]. The generation of balanced three-phase sinusoidal power from DC sources is explained in Chapter 15.

10.3. Connections of three-phase circuits

The three-phase sources can be connected either in delta or wye (or star-Y). Similarly the three-phase load can be connected either in delta or wye [4,5].

10.3.1. Wye-connected balanced source

A wye-connected balanced source is shown in Figure 10.2. In Y connection, the common terminal “n” is known as the neutral terminal of the source. Zsa, Zsb, and Zsc are the source impedance of the sources in phases a, b, and c. For balanced sources, Zsa = Zsb = Zsc = Zs. The voltages va, vb, and vc are the source internal voltages (or the induced emf [electromotive force]) of the three phases a, b, and c. For balanced source, all three voltages will have the same frequency and amplitude, and are phase displaced by 120° (2π/3 rad) as defined in (10.1).
image
Figure 10.2 Wye-connected balanced source.

10.3.1.1. Phase voltages

Phase voltages are the voltages at the terminals “a,” “b,” and “c” measured with reference to neutral point “n.”
In Figure 10.2, under open circuit conditions:

van=Vmsinωtvbn=Vmsinωt2π3vcn=Vmsinωt4π3

image(10.2)
The phase voltages in phasor form are:

Van=V0°,Vbn=V120°andVcn=V240°

image
where V is the RMS value of the phase voltage and V=Vm2image.
Under balanced conditions, van + vbn + vcn = 0 and Van + Vbn + Vcn = 0.

10.3.1.2. Line voltages

The voltage difference between two line terminals or two phases is the line voltage. Following the Kirchhoff’s voltage law, line voltages vab, vbc, and vca can be expressed in terms of phase voltages as in (10.3):

vab=vanvbn=VmsinωtVmsinωt2π3=3Vmsinωt+π6vbc=vbnvcn=Vmsinωt2π3Vmsinωt4π3=3Vmsinωtπ2vca=vcnvan=Vmsinωt4π3Vmsinωt=3Vmsinωt7π6

image(10.3)
The line voltages in phasor form are:

Vab=VL30°,Vbc=VL90°andVca=VL210°,

image
where VL is the RMS value of the line voltage and VL=3Vm2=3|V|image.
Note: Under balanced conditions, vab + vbc + vca = 0 and Vab + Vbc + Vca = 0.
The phasor diagram of the phase voltages and line voltages in a wye-connected source is shown in Figure 10.3.
image
Figure 10.3 Phasor diagram of line and phase voltage vectors of wye-connected sources.

10.3.1.3. Phase currents

The current flowing in the source winding or the source is the phase current. Let us assume that the phase current in the source is given by (10.4)

ia=Imsinωtθib=Imsinωt2π3θic=Imsinωt4π3θ

image(10.4)
where θ is the phase angle between the phase voltage and corresponding phase current. In phasor form the above can be written as:

Ia=Iθ°,Ib=I120°θ°, and Ic=I240°θ°,

image
where I=Im2image. Note:ia+ib+ic=0image

10.3.1.4. Line currents

The current flowing out of the terminals is known as the line current. For a wye-connected source the line current is equal to the phase current:

ILa=Ia, ILb=Ib, ILc=Ic, and IL=I

image(10.5)
Note: In a balanced wye-connected system:
The line voltage leads the corresponding phase voltage by 30° and the magnitude of the line voltage is 3image times the magnitude of the phase voltage.
The phase current is equal to the line current.

10.3.2. Delta-connected balanced source

A delta-connected balanced source is shown in Figure 10.4. Zsa, Zsb, and Zsc are the source impedance of phases a, b, and c and for balanced sources, Zsa = Zsb = Zsc = Zs. The voltages va, vb, and vc are internal voltages of the source (or the induced emf) of the three phases a, b, and c. For balanced source, all three voltages will have the same frequency, equal amplitude, and phase displaced by 120° (2π/3 rad) as defined in (10.1).
image
Figure 10.4 Delta-connected balanced source.

10.3.2.1. Line voltages

The windings of each phase in delta connections now appear between two lines as shown in Figure 10.4. Under open-circuit conditions, the phase voltage for a delta-connected source is given by:

vab=va=Vmsinωtvbc=vb=Vmsinωt2π3vca=vc=Vmsinωt4π3

image(10.6)
The line voltages in phasor form are:

Vab=VL0°,Vbc=VL120°,andVca=VL240°

image
where VL is the RMS value of the line voltage and VL=Vm2image.
Note: vab+vbc+vca=0soicir=0image.

10.3.2.2. Phase voltages

For a delta-connected source, the phase voltages are equal to line voltages:

V=VL

image(10.7)

10.3.2.3. Phase currents

The current flowing in the source winding or the source is the phase current. Let us assume that the phase current in the source is given by (10.8):

ia=Imsinωtθib=Imsinωt2π3θic=Imsinωt4π3θ

image(10.8)
where θ is the phase angle between the phase voltage and corresponding phase current. The phase currents in phasor form are:

Ia=Iθ°,Ib=I(120°θ)°andIc=I240°θ°,whereI=Im2.

image

10.3.2.4. Line currents

The current flowing out of the terminals is the line current. For a delta- connected source the line current is given by (10.9).
Applying Kirchhoff’s current law at nodes a, b, and c, respectively, we get:

iLa=iaic=ImsinωtθImsinωt2π3±θ=3Imsinωtπ6±θiLb=ibia=Imsinωt2π3±θImsinωt±θ=3Imsinωt5π6±θiLc=icib=Imsinωt4π3±θImsinωt±θ=3Imsint3π2±θ

image(10.9)
The line currents of a delta-connected source in phasor form are written as:

ILa=IL±θ°,ILb=IL120°±θ°andILc=IL240°±θ°,whereIL=3|I|=Im2

image
Note: In a balanced delta-connected system:
The line current lags the corresponding phase current by 30° and the magnitude of the line current is 3image times the magnitude of the phase current.
The phase voltage is equal to the line voltage.
The phasor diagram of voltages and currents in a delta-connected source is given in Figure 10.5.
image
Figure 10.5 Phasor diagram of line currents and phase currents in a delta-connected source.

10.3.3. Wye-connected balanced load

A wye-connected load is shown in Figure 10.6. A, B, and C are the terminals of phase a, phase b, and phase c, respectively The three loads are connected at common point “N” called the neutral point of the load. ZA, ZB, and ZC are the source impedance of phases a, b, and c. For a balanced load, ZA = ZB = ZC = Z. If we take the phase voltage VAN as reference, then

VAN=V0°,VBN=V120°andVCN=V240°.

image
image
Figure 10.6 Wye-connected load.
The line voltages are:

VAB=VANVBN=3|V|30°=VL30°,VBC=VBNVCN=3|V|90°=VL90°,VCA=VCNVAN=3|V|210°=VL210°andVL=3V

image
When a wye-connected balanced load is supplied by the balanced source then the phase currents in the load will also be balanced.

IA=I±θ°,IB=I120°±θ°,andIC=I240°±θ°,

image
where θ is the impedance angle, same as the phase angle between the phase voltage and the load current.
For a wye-connected load, the line currents are given by: iLA=iA,iLB=iB, iLC=iC,andIL=Iimage.

10.3.4. Delta-connected balanced load

A delta-connected load is shown in Figure 10.7. A, B, and C are the terminals of phase a, phase b, and phase c, respectively. ZA, ZB, and ZC are the respective load impedances. For balanced sources, ZA = ZB = ZC = Z. When the balanced load is supplied by a balanced source, the line currents as well as the phase currents in the load are balanced.
image
Figure 10.7 Delta-connected load.
For a delta-connected load, the line voltages are given by:

VAB=VL0°,VBC=VL120°,andVCA=VL240°,

image
For a delta-connected load, VL = V.
When a delta-connected balanced load is supplied by a balanced source then the phase currents in the load will also be balanced:

IA=I±θ°,IB=I120°±θ°,andIC=I240°±θ°,

image
where θ is the impedance angle.
For a delta-connected load, the line currents are given by:

ILA=IAIB=3I30±θ°ILB=IBIC=3I150±θ°ILC=ICIA=3I270±θ°andIL=3I

image

10.4. Circuits with mixed connections

There are mainly four types of networks in three-phase systems and these are listed in Table 10.1.

Table 10.1

Types of three-phase networks

Type of connection Source Load
Wye–wye connection Wye Wye
Wye–delta connection Wye Delta
Delta–wye connection Delta Wye
Delta–delta connection Delta Delta
The delta-connected source or load can be transformed into an equivalent wye-connected source or load, respectively [4,5]. Hence, all the other three connections can be analyzed by converting them into an equivalent wye–wye network. In the following subsection analysis of a wye–wye network is presented.

10.4.1. Wye–wye network

Line currents (IL) are the currents flowing in each line and phase current (I) is the current flowing in an individual source or load. For simplicity we limit our analysis to passive loads, that is, loads consisting of R, L, and C components only.
The circuit in Figure 10.8 shows a typical wye–wye network of the power system.
image
Figure 10.8 Wye–wye network.
Zsa = Zsb = Zsc = Zs and ZLa = ZLb = ZLc = ZL are the impedances of the line connecting the source to load; these are equal and referred to as line impedances.
ZA = ZB = ZC = Z are the load impedances connected in wye. N is the neutral point of the load.
Applying Kirchhoff’s current law at source neutral “n,” the node equation is:

Va'nVNnZsa+ZLa+ZAVb'nVNnZsb+ZLb+ZB+Vc'nVNnZsc+ZLc+ZC=VNnZLnVa'n+Vb'n+Vc'nZs+ZL+Z=VNnZLn+VNnZs+ZL+Z

image
For a balanced source Va'n+Vb'n+Vc'n=0image:

VNnZLn+VNnZs+ZL+Z=0

image
So, for a balanced three-phase circuit, VNn = 0.
This means that there is no voltage difference between the source neutral “n,” and the load neutral “N.” Consequently, IN = 0, Hence, we can remove the neutral line from the balanced wye–wye configuration resulting in a three-phase –three-wire wye–wye connection or we can connect n to N resulting in a three-phase–four-wire wye–wye connection [1,4,5].

10.4.1.1. Line currents and phase currents

The line currents (ILA, ILB, and ILC) are the currents flowing out of source terminals and into the load terminals through the line impedance.
In Figure 10.8, the voltages at the source in each phase are defined as:
Va'n=V0°,Vb'n=V120°,andVc'n=V240°image
The voltage Va'nimage is taken as the reference vector.
Let us define:

Z=Zs+ZL+Z=Zθ

image

IsA=ILA=IA=Va'nZsa+ZLa+ZA=VZsa+ZLa+ZA=V(0)°Z=I°,whereI=VZ

image

IsB=ILB=IB=Vb'nZsb+ZLb+ZB=VZsb+ZLb+ZB=V0°°Z=I°IsC=ILC=IC=Vc'nZsc+ZLc+ZC=VZsc+ZLc+ZC=V0°°Z=I°IA+IB+IC=0

image
For a wye-connected load or source, the line current = phase currents.
So IL = I.
Note: For a balanced three-phase wye–wye network:
The load currents are balanced, that is, they are equal in magnitude and phase displaced by 120°.
There is no current in the neutral wire.
We can represent the previously mentioned system by an equivalent per phase network using phase quantities. The per phase equivalent circuit for any one phase (say, for phase a) is given in Figure 10.9.
image
Figure 10.9 Per-phase equivalent circuit.

10.4.1.2. Line voltages at the load terminals

In Figure 10.8, the phase voltages at load terminal are given by:

VAN=IAZVBN=IBZVCN=ICZ

image
It can be seen that all the three-phase voltages are balanced.

VAN+VBN+VCN=0

image
The line voltages are given by:

VAB=VANVBNVBC=VBNVCNVCA=VCNVAN

image
It can be seen that all the three-line voltages are balanced. Hence, VAB + VBC + VBC = 0 and as seen in Section 10.3.1, the line voltages will be leading the corresponding phase voltage by 30° and VL=3Vimage.

10.4.1.3. Line voltages at the source terminals

In Figure 10.8, the phase voltages at the phase terminal are given by:

Van=Va'nIsaZsa=Va'nIAZsVbn=Vb'nIsbZsb=Vb'nIBZsVcn=Vc'nIscZsc=Vc'nICZs

image
It can be seen that all the three-phase voltages are balanced:

Van+Vbn+Vcn=0

image
The line voltages at the source terminals are given by:

Vab=VanVbnVbc=VbnVcnVca=VcnVan

image
It can be seen that all the three-line voltages are balanced.
As seen in Section 10.3.1, the line voltage is leading the corresponding phase voltage by 30° and VL=3Vimage.

Example 10.1

A balanced three-phase wye-connected generator has an internal impedance of 0.2 + j0.5 Ω per phase and the phase to neutral voltage is 220 V. The generator feeds a balanced three-phase wye-connected load having a load impedance of 10 + j8 Ω in each phase. The impedance of the line connecting the generator to the load is 0.2 + j0.8 Ω in each line. The a-phase internal voltage of the generator is specified as the reference phasor.
1. Construct a phase equivalent circuit of the system.
2. Calculate the line currents ILA, ILB, and ILC.
3. Calculate the phase voltages at the load, VAN, VBN, and VCN.
4. Calculate the line voltages VAC, VBC, and VCA at the load terminals.
5. Calculate the phase voltages at the generator terminals, Van, Vbn, and Vcn.
6. Calculate the line voltages at the generator terminals, Vab, Vbc, and Vca.

Solution

1. a-Phase equivalent circuit (Figure 10.10):
2. Line currents ILA, ILB, and ILC:

ILA=VanZ=2200°0.2+0.2+10+j0.5+0.8+8=2200°13.9541.8°=15.7741.8° AILB=15.7741.8°120°=15.77161.8° AILC=15.7741.8°+120°=15.7778.2° A

image
3. Phase voltages at the load, VAN, VBN, and VCN:

VAN=ILAZA=15.7741.8°10+j8=2023.14° VVBN=2023.14°120°=202123.14° VVCN=2023.14°+120°=202116.86° V

image
4. Line voltages VAB, VBC, and VCA at the load terminals:

VAB=3VAN30°=3×2023.14°+30°=349.926.86° VVBC=3VBN30°=3×202123.14°+30°=349.993.14° VVCA=3VCN30°=3×202116.86°+30°=349.9146.86° V

image
5. Phase voltages at the generator terminals, Van, Vbn, and Vcn.
Phase current in the source = ILA:

Van=2200°IsaZs=2200°15.7741.8°0.2+j0.5=212.431.02° VVbn=212.431.02°120°=212.43121.02° VVcn=212.431.02°+120°=212.43118.98° V

image
6. Line voltages at the generator terminals, Vab, Vbc, and Vca:

Vab=3Van30°=3×212.431.02°+30°=367.9428.98° VVbc=3Vbn30°=3×212.43121.02°+30°=367.9491.02° VVbc=3Vbn30°=3×212.43118.98°+30°=367.94148.98° V

image
image
Figure 10.10 Per-phase circuit for Example 10.1.

10.4.2. Delta to wye conversion

A delta-connected load (or source) can be converted to a wye-connected load (or source) and vice versa. This transformation is particularly useful to convert all the other types of configurations to get equivalent wye–wye configurations.
Assume that ZD is the load connected in delta as shown in Figure 10.11. The supply voltage is VAB=V0°,VBC=V120°, and VCA=V240°image.
image
Figure 10.11 Delta-connected load and its wye equivalent.
Let us use the principle of superposition by considering only one source at a time. First consider source VAB:

VAB=V0°;VBC=0(opencircuit);VCA=0(opencircuit)

image
The current due to the delta-connected load is:

ILA=VABZD||2ZD

image
Let ZY be the equivalent wye-connected load in each phase supplied from the same source.
The current due to the wye-connected load is:

ILA=VABZY+ZY

image
Both the currents should be equal, hence:

VAB(ZD×2ZD)/3ZD=VAB2ZY32ZD=12ZY3ZY=ZDZY=ZD3

image(10.10)

10.4.3. Wye-connected source/delta-connected load

The wye-connected source and delta-connected load are shown in Figure 10.12. The delta-connected load can be replaced by an equivalent wye-connected load using delta to wye conversion. In Figure 10.12, for a balanced load the load in each phase, ZA = ZB = ZC = ZD.
image
Figure 10.12 Wye-connected source and delta-connected load.
Using equation (10.9), the previously mentioned load can be replaced by an equivalent wye-connected load of ZY=ZD3image.
Now the resulting wye–wye network can be solved using the procedure given in Section 10.4.1.
The magnitude load current in each phase in a delta-connected load is given by I=IL3image and the phase current will be leading the line current by 30°.

Example 10.2

A balanced three-phase wye-connected generator has an internal impedance of 0.2 + j0.5 Ω/Ø and an internal voltage 220 V per phase. The generator feeds a delta-connected load having an impedance of 30 + j24 Ω in each phase. The impedance of the line connecting the generator to the load is 0.1 + j0.9 Ω in each line. The a-phase internal voltage of the generator is specified as the reference phasor.
1. Construct the a-phase equivalent circuit of the system.
2. Calculate the line currents ILA, ILB, and ILC.
3. Calculate the phase voltages at the load, VAN, VBN, and VCN.
4. Calculate the phase currents of the load.
5. Calculate the line voltages at the generator terminals, Vab, Vbc, and Vca.

Solution

1. Construct the a-phase equivalent circuit of the system (Figure 10.13):

ZY=ZD3=30+j243=10+j8

image
2. Line currents ILA, ILB, and ILC:

ILA=VanZ=2200°0.2+0.1+10+j0.5+0.9+8=2200°1442.38°=15.7842.38° AILB=15.7842.38°120°=15.78162.38° AILC=15.7842.38°+120°=15.7877.62° A

image
3. Phase voltages at the load, VAN, VBN, and VCN:

VAN=IaAZY=15.7842.38°10+j8=2023.72° VVBN=2023.72°120°=202123.72° VVCN=2023.72°+120°=202116.38° V

image
4. Phase currents of the load IAB, IBC, and ICA:

IA=IaA30°3=15.7842.38°+30°3=9.1112.38°AIB=9.1112.38°120°=9.11132.38°AIC=9.1112.38°+120°=9.11107.62°A

image
5. Line voltages at the generator terminals Vab, Vbc, and Vca.
We start by calculating the phase voltages at the generator terminals, Van, Vbn, and Vcn:

Van=2200°ILAZan=2200°15.7742.38°0.2+j0.5=212.380.998° VVab=3Van30°=3×212.380.998°+30°=367.8629.002° VVbc=367.8629.002°120°=367.8690.998° VVca=367.8629.002°+120°=367.86149.002° V

image
image
Figure 10.13 Single-phase equivalent circuit for Example 10.2.

10.4.4. Delta–wye network

The delta–wye network is shown in Figure 10.14. The delta-connected source can be represented by the equivalent wye-connected source. The resulting equivalent circuit can be solved similar to the wye–wye network.
image
Figure 10.14 The delta–wye network.

10.4.5. Delta–delta network

The delta–delta network is shown in Figure 10.15. The delta-connected source and delta-connected load can be represented by the equivalent wye-connected source and wye-connected load, respectively. The resulting equivalent circuit can be solved similar to the wye –wye network.
image
Figure 10.15 The delta–delta network.

10.5. Power calculation of balanced three-phase circuit

10.5.1. Balanced wye loads

Consider a wye-connected balanced load (refer to Figure 10.6) with load impedance in each phase, Z=Z±θimage.
Phase voltage across the load is V=V0°image.
Current in the load in each phase is I=VZimage.

Active power per phase:P=VIcosθ

image(10.11)

Reactive power per phase:Q=VIsinθ

image(10.12)

Apparent power per phase:S=P+jQ,S=VI

image(10.13)
In a wye-connected system:

VL=3VandIL=I

image
Total active power in a three-phase circuit:

P=3P=3VIcosθ=3VLILcosθ

image(10.14)
Total reactive power in a three-phase circuit:

Q=3Q=3VIsinθ=3VLILsinθ

image(10.15)
Total apparent power in three phases:

S=P+jQ,S=3VI=3VLIL

image(10.16)

10.5.2. Balanced delta loads

Consider a delta-connected balanced load (refer to Figure 10.7) with load impedance in each phase, Z=Z±θimage.
Active and reactive power consumed by the load across nodes A and B is:

PAB=VABIAcosθQAB=VABIAsinθ

image
Active and reactive power consumed by the load across nodes B and C is:

PBC=VBCIBcosθQBC=VBCIBsinθ

image
Active and reactive power consumed by the load across nodes C and A is:

PCA=VCAICcosθQCA=VCAICsinθ

image

VAB=VBC=VCA=VIA=IB=IC=I

image
The total active and reactive power consumed by the three-phase delta-connected load is:

P=PAB+PBC+PCA=3VIcosθQ=SAB+SBC+SCA=3VIcosθ

image
In delta-connected system, VL=VandIL=3Iimage.

P=3VIcosθ=3VLILcosθ

image(10.17)

Q=3VIsinθ=3VLILsinθ

image(10.18)

S=P+jQS=3VI=3VLIL

image(10.19)

Example 10.3

Consider the wye–wye network in Example 10.1:
1. Calculate the active power, reactive power, and apparent power in each phase of the load.
2. Calculate the total active power, reactive power, and apparent power consumed by the load.
3. Calculate the total active power, reactive power, and apparent power supplied by the source.

Solution

Load current IA=15.7741.8° Aimage.
Phase voltage at load terminals is VAN=2023.14° Vimage.
1. Calculate the active power, reactive power, and apparent power in each phase of the load:

P=VIcosθ=202×15.77×cos41.8°3.14°=202×15.77×cos38.66°=2.487 kWQ=VIsinφ=202×15.77×sin41.8°3.14°=202×15.77×sin38.66°=1.989 kVARS=VI=202×15.77=3.185 kVA

image
2. Calculate the total active power, reactive power, and apparent power consumed by the load:

P=3P=3×2.487=7.461 kWQ=3S=3×1.989=5.967 kVARS=3S=3×3.185=9.555 kVA

image
3. Calculate the total active power, reactive power, and apparent power supplied by the source.
Source current = ILA=15.7741.8° Aimage.
Phase voltage at source Van=2200° Vimage.

P=3VIcosθ=3×220×15.77×cos41.8°=7.759kWQ=3VIsinθ=3×220×15.77×sin41.8°=6.937kVARS=3VI=3×220×15.77=10.408kVA

image

Example 10.4

Consider the wye–delta network in Example 10.2:
1. Calculate the active power, reactive power, and apparent power in each phase of the load.
2. Calculate the total active power, reactive power, and apparent power consumed by the load.
3. Calculate the total active power, reactive power, and apparent power supplied by the source.

Solution

1. Calculate the active power, reactive power, and apparent power in each phase of the equivalent wye connected load
Iφ=15.7842.38°A
image
Vφ=2023.72°V
image
For delta-connected load.
Phase voltage = voltage across load,
VAB=3VAN30°=3×202×(3.72+30)°=349.8726.28°
image
Load current per phase

IAB=Iφ3(θ+30)A

image

IAB=9.1112.38°A

image

Pφ=VφIφcosθ

image

=349.87×9.11×cos(26.28°+12.38°)=349.87×9.11×cos(38.66°)=2.488 kW

image

Qφ=VφIφsinθ

image

=349.87×9.11×sin(26.28°+12.38°)=1.990 kVAR.

image

Sφ=VφIφ=348.87×9.11=3.186 kVA

image
2. Calculate the total active power, reactive power, and apparent power consumed by the load.

P=3Pφ=3×2.487=7.461 kW

image

Q=3Sφ=3×1.901=5.703 kVAR

image

S=3Sφ=3×3.186=9.558 kVA

image
3. Calculate the total active power, reactive power, and apparent power consumed by the source.
Voltage per phase at source Vφ=2200°Vimage
Phase current in source Iφ=IA=15.7842.38°image A

P=3VφIφcos=3×220×15.78×cos(42.38°)=7.693 kW

image

Q=3VφIφsinθ=3×220×15.78×sin(42.38°)=7.020 kVAR

image

S=3VφIφ=3×220×15.78=10.414 kVA

image

10.6. Advantages and disadvantages of three-phase supply

10.6.1. Advantages

Power transmission will be three times that of a single-phase supply.
Higher reliability: if one or two of the phases fail, the healthy phase can supply power.
Two voltage levels: possible to connect single-phase and three-phase with two voltage levels (line and phase).

10.6.2. Disadvantages

Three lines are required; expensive compared to single phase.
Difficult to maintain exact balanced load when single-phase and three-phase loads are used.

10.7. Summary

In a balanced three-phase system, all the three phases or line voltages will have the same frequency, equal voltage magnitude, and are phase displaced by 120°.
In a balanced three-phase system, all the three phases or line currents will have the same frequency, equal voltage magnitude, and are phase displaced by 120°.
In a wye-connected system the magnitude of the line voltage will be 3image times the magnitude of the phase voltage and the line voltage will lead the corresponding phase voltage by 30°. The line current is equal to the phase current.
In a wye-connected system the magnitude of the line current will be 3image times the magnitude of the phase current and the line current will lag the corresponding phase current by 30°. The line voltage is equal to the phase voltage.
In a balanced three-phase system the sum of all three-phase (line) voltages is equal to zero and the sum of all three phase (line) currents is equal to zero.
A balanced wye–wye circuit can be reduced to a single-phase equivalent single-phase circuit and can be analyzed similar to a single-phase circuit using per phase quantities.
A delta-connected source or load can be converted to an equivalent wye-connected source or load. So the wye–delta, delta–wye, and delta–delta network can be converted to an equivalent wye–wye network.

Problems

1. For each set of voltages, state whether or not the voltages form a balanced three-phase set. If the set is not balanced, explain why.
a. Va=156cos314tV,Vb=156cos314t120°V,Vc=156cos314t+120°V.image
b. Va=6002sin377tV,Vb=6002sin377240°V,Vc=6002sin377+240°V.image
c. Va=1796sinωt+10°V,Vb=1796cosωt110°V,Vc=2796cosωt+130°V.image
2. The time domain expressions for the three line-to-neutral voltages at the terminals of a wye-connected load are:
VAN=1796cosωt V,VBN=1796cosωt+120°V,VCN=1796cosωt120°V.
image
Write the time domain expressions for the three line-to-line voltages vAB, vBC, and vCA.
3. The magnitude of the phase voltage of an ideal balanced three-phase wye-connected source is 2200 V. The source is connected to a balanced wye-connected load by a distribution line that has an impedance of 2 + j16 per line. The load impedance is 20 + j40 Ω in each phase. The phase sequence of the source is a–b–c. Use the a-phase voltage of the source as the reference. Specify the magnitude and phase angle of the following quantities:
a. The three line currents.
b. The three line voltages at the source.
c. The three phase voltages at the load.
d. The three line voltages at the load.
4. A balanced delta-connected load is powered from a wye-connected source. The load impedance is 36 + j10 Ω in each phase. The line impedance of each line connecting the source to the load is 0.1 + j1 Ω. The line voltage at the terminals of the load is 33 kV.
a. Calculate the three phase currents of the load.
b. Calculate the three line currents.
c. Calculate the three line voltages at the source.
5. In a balanced three-phase system, the source is balanced wye with line voltage = 190 V. The load is a balanced wye in parallel with a balanced delta. The phase impedance in each phase of the wye-connected load is 4 + j3 Ω and the impedance of the delta is 3 – j9 Ω per phase. The line impedance is 1.4 + j0.8 Ω per line.
a. Calculate the current in the wye-connected load.
b. Calculate the current in the delta-connected load.
c. Calculate the current in the source.
6. The delta-connected source is connected to a wye-connected load. The load impedance per phase is 100 + j200 Ω, and the line impedance is 1.2 + j12 Ω. The line voltage of the source is 6600 V. Ignore the internal impedance of the source.
a. Construct a single-phase equivalent circuit of the system.
b. Determine the magnitude of the line voltage at the terminals of the load.
c. Determine the magnitude of the phase current in the delta-connected source.
7. A three-phase delta-connected generator has an internal impedance of 0.6 + j4.8 Ω per phase with an open-circuit terminal voltage of 33,000 V. The generator feeds a delta-connected load through a transmission line with an impedance of 0.8 + j6.4 Ω. The impedance of the load is 2877 – j864 Ω per phase.
a. Calculate the magnitude of the line current.
b. Calculate the magnitude of the line voltage at the terminals of the load.
c. Calculate the magnitude of the line voltage at the terminals of the source.
d. Calculate the magnitude of phase current in the load.
e. Calculate the magnitude of phase current in the source.
8. The output of the balanced positive-sequence three-phase source is 100 kVA and power factor is 0.8 lead. The line voltage at the source is 400 V. The impedance of each line connecting the source to the load is 0.05 + j0.2 Ω.
a. Find the magnitude of the line voltage at the load.
b. Find the total complex power at the terminals of the load.
9. A balanced wye-connected load is supplied from a balanced three-phase voltage source. The three-phase voltage source is 220 V. Load impedance is 8 + j6 Ω at 50 Hz. Neglect the source internal impedance and impedance of the line connecting the source and load. Find the current in the load and source.
10. The current in a balanced wye-connected load is 8 A. The source is wye connected with a phase voltage of 230 V. The load power factor is 0.8 lagging. Neglect the source internal impedance and impedance of the line connecting the source and load. Find the resistance and reactance of the load.
11. The p and Q in a three-phase wye-connected system are 1000 W and 1000 VAR, respectively. The source voltage is 220 V. Neglect the source internal impedance and impedance of the line connecting the source and load. Find the impedance per phase and current.
12. Show that the total instantaneous power in a balanced three-phase circuit is constant and equal to 1.5VmIm cos θ, where Vm and Im represent the maximum amplitudes of the phase voltage and phase current, respectively.
13. A balanced three-phase source is supplying 90 kVA at 0.8 lagging to two balanced wye-connected parallel loads. The distribution line connecting the source to the load has negligible impedance. Load 1 is purely resistive and absorbs 60 kW. Find the per-phase impedance of load 2 if the line voltage is 415.69 V and the impedance components are in series.
14. The total apparent power supplied in a balanced three-phase wye–delta system is 10 kVA. The line voltage is 190 V. if the line impedance is negligible and the power factor angle of the load is 25°, determine the impedance of the load.
15. In a balanced three-phase system, the source has an a–b–c sequence, is wye connected, and Van = 110 ∠ 20° V. The source feeds two loads, both of which are wye connected. The impedance of load 1 is 8 + j6 Ω per phase. The complex power for the a-phase of load 2 is 600 ∠ 36° VA. Find the total complex power supplied by the source.

References

[1] Hayt W, Buck J. Engineering electromagnetics. 8th ed. New York: McGraw-Hill International Edition; 2011.

[2] Chapman SJ. Electric machinery fundamental. New York: McGraw-Hill International Edition; 2005.

[3] Nilsson J, Riedel SA. Electric circuits. 9th ed. New Jersey: Pearson International Edition; 2011.

[4] Dorf RC, Sroboda JA. Introduction to electric circuits. New Jersey: John Wiley and Sons, Inc.; 2006.

[5] Rashid MH. Power electronics – circuits, devices and applications. 4th ed. New Jersey: Pearson International Edition; 2013.

..................Content has been hidden....................

You can't read the all page of ebook, please click here login for view all page.
Reset